Menu 3 - Analog I/O; Parameter - Emerson SI-I/O User Manual

Table of Contents

Advertisement

How to use this
Safety
Introduction
guide
information
7.4

Menu 3 - Analog I/O

Menu 3 on the module controls and displays all parameters associated with the Analog I/O.
S.03.001
Analog Input 1
S.03.002
Analog Input 2
S.03.003
Analog Input 3
Minimum
-100.00
Default
Type
16 Bit Volatile
Display Format
None
Coding
RO, FI, ND, NC, PT
Analog inputs 1, 2 and 3 have a resolution of 12 bits. The input can operate in different modes as defined the mode selected in Pr S.01.015 to Pr
S.01.017 including current modes.
The "Input Level" is defined for the different modes as shown in the table below.
Mode
Volt IN
(Input Voltage / 10 V) x 100.00 %
0-20mA
(Input Current / 20 mA) x 100.00 %
20-0mA
((20 mA – Input Current) / 20 mA) x 100.00 %
4-20mA
((Input Current – 4 mA) / 16 mA) x 100.00 %
20-4mA
((20 mA – Input Current) / 16 mA) x 100.00 %
Analog Inputs 1-3 (Pr S.03.001 to Pr S.03.003) are derived as follows (Analog Input 1 is used for this example):
A
is the value after the minimum and maximum limits are applied.
1
If Analog Input 1 Minimum (Pr S.03.014) ≥ Analog Input 1 Maximum (Pr S.03.015) then: A
If Analog Input 1 Minimum (Pr S.03.014) < 0.00% and Analog Input 1 Maximum (Pr S.03.015) > 0.00 % then:
Input Level is limited between - Analog Input 1 Minimum (Pr S.03.014) and + Analog Input 1 Maximum (Pr S.03.015).
A
= Input Level x (100.00 % / Analog Input 1 Maximum (Pr S.03.015)
1
Otherwise:
Input Level is limited between Analog Input 1 Minimum (Pr S.03.014) and Analog Input 1 Maximum (Pr S.03.015).
A
= [(Input Level - Analog Input 1 Minimum (Pr S.03.014)) x 100.00 %] / [Analog Input 1 Maximum (Pr S.03.015) - Analog Input 1 Minimum (Pr
1
S.03.014)].
S.03.004
Differential Analog Input
Minimum
-100.0000
Default
Type
32 Bit Volatile
Display Format
None
Coding
RO, ND, NC, PT
The Differential Analog Input has a resolution of 16 bits. The minimum resolution of Pr S.03.004 is 0.0030518 % (100 / 215 %).
The level of Differential Analog Input (Pr S.03.004) is calculated in the same way as Analog Inputs 1-3 (Pr S.03.001 - Pr S.03.003).
NOTE
The differential analog input is only available on Unidrive M600 - M800.
S.03.005
Analog Output 1
Minimum
-100.00
Default
0.00
Type
16 Bit Volatile
Display Format
None
Coding
RO, PT
Analog Output 1 (Pr S.03.005) has a resolution of 12 bits plus sign. Analog Output 1 (Pr S.03.005) shows the value passed by Analog Output 1
Source (Pr S.03.006) which is then scaled by Analog Output 1 Scaling (Pr S.03.007) and clamped between -100.00 and 100.00%.
NOTE
The analog output is only available on Unidrive M600 - M800.
24
Mechanical
Electrical
Single line
installation
installation
descriptions
Maximum
100.00
Units
%
Update Rate
250 µs write
Decimal Places
2
Input Level
Maximum
100.0000
Units
%
Update Rate
4 ms write
Decimal Places
4
Maximum
100.00
Units
%
Update Rate
Background read
Decimal Places
2
Parameters
Block diagrams
Diagnostics
= 0.00 % whatever the input level is.