Emerson Spence Type N6 Instruction Manual

Emerson Spence Type N6 Instruction Manual

Differential pressure valves

Advertisement

Quick Links

Instruction Manual
VCIMD-16088
November 2021
Spence Type N6 Differential Pressure Valves
Failure to follow these instructions or
to properly install and maintain this
equipment could result property damage
and personal injury or death.
Type N6 differential pressure valves
must be installed, operated and
maintained in accordance with federal,
state and local codes, rules and
regulations and Emerson Process
Management Regulator Technologies,
Inc. (Emerson) instructions.
If the valve vents gas or a leak develops
in the system, service to the unit may be
required. Failure to correct issue could
result in a hazardous condition.
Installation, operation and maintenance
procedures performed by unqualified
personnel may result in improper
adjustment and unsafe operation. Either
condition may result in equipment
damage or personal injury. Only a
qualified person shall install or service
the Type N6 differential pressure valves.
Introduction
Scope of the Manual
This manual provides instructions for the installation,
troubleshooting, maintenance, valve setting and parts
ordering for Type N6 differential pressure valves.
Product Description
Type N6 differential pressure valves are designed
to maintain pump discharge pressures at a constant
differential above a separate source of pressure.
When installed in a boiler feed pump discharge line
WARNING
Figure 1. Type N6 Differential Pressure Valves
as a by-pass valve, a connection from the stream
drum is made to the top chamber of the Type N6.
The desired differential is made by adjusting the
spring. The boiler feed-water pressure will then be
maintained by Type N6 at a constant pressure above
steam drum pressure by modulating the quantity of
water by-passed to pump section. When installed in
a by-pass line across a pumped system, Type N6
will maintain a constant differential of supply main
pressure over return main pressure by modulating the
quantity of by-passed water.
www.SpenceValve.com
www.SpenceValve.com
Type N6

Advertisement

Table of Contents
loading

Summary of Contents for Emerson Spence Type N6

  • Page 1 Instruction Manual Type N6 VCIMD-16088 November 2021 Spence Type N6 Differential Pressure Valves ▲ WARNING Failure to follow these instructions or to properly install and maintain this equipment could result property damage and personal injury or death. Type N6 differential pressure valves...
  • Page 2: Specifications

    Type N6 Specifications This section lists the specifications for the Type N6 differential pressure valves. Factory specifications are stamped on the nameplate fastened on the valve at the factory. Valve Sizes Rated Flow Coefficient NPS 3/4, 1, 1-1/4, 1-1/2, 2 and 2-1/2 / See Table 1 Materials of Construction DN 20, 25, 32, 40, 50 and 65...
  • Page 3: Principle Of Operation

    Type N6 BOILER DRUM PRESSURE BOILER LEVEL CONTROL VALVE 1/4 IN. PIPE BOILER FEED TANK BOILER WATER FEED LINE TYPE N6 VALVE BY-PASS LINE FEED PUMP Figure 2. Type N6 Installation Drawing Principle of Operation force creates the differential between the retained Flow enters the valve such that the initial pressure acts against the working face of the disk and tends to move pressure (supply main or boiler feed water) under the...
  • Page 4: Installation

    Specifications • Avoid damaging effects of foreign matter in the flow section and/or valve nameplate. by using Emerson strainer ahead of the valve. Additionally, physical damage to the Startup and Adjustment valve may result in personal injury or property damage due to escaping of 1.
  • Page 5: Valve Grinding

    Only parts manufactured by 2. Check seating by blueing the valve disk bevel face Emerson should be used for repairing before reassembling. this valve. 3. Clean all parts with kerosene or carbon Under normal conditions, complete dismantling tetrachloride before reassembling.
  • Page 6: Parts Ordering

    Type N6 Parts Ordering Parts List Type N6 When corresponding with your local Sales Office about this See Table 3 equipment, always reference the equipment serial number that can be found on the nameplate. When ordering replacement parts, reference the key number of each needed part as found in the following parts list.
  • Page 7 Type N6 1/4 NPT SERIAL NUMBER PLATE Figure 3. Type N6 Assembly Drawing...
  • Page 8 SpenceValve.com VCIMD-16088 © 2021 Emerson Electric Co. All rights reserved. 11/21 Spence is a mark owned by one of the companies in the Emerson Automation Emerson Automation Solutions Solutions business unit of Emerson Electric Co. The Emerson logo is a trademark and service mark of Emerson Electric Co.

Table of Contents