Menu 1 - I/O Set-up

Menu 1 contains all the parameters relating to the setup of the I/O interface on the SI-I/O module.
S.01.001
Reset I/O Interface
Minimum
0
Default
0
Type
1 Bit Volatile
Display Format
None
Coding
RW, NC
Changes to the module's configuration will not take effect until the module has been reset.
To reset the module:
Set Pr S.01.001 to On (1).
When the sequence has been completed, Pr S.01.001 will be reset to Off (0).
The module will reset using the updated configuration.
NOTE
This sequence does NOT store the module's configuration parameters in the drive or the module's flash memory. This parameter will change back to
Off immediately, and as such the change may not be visible in the display.
S.01.002
Default I/O Interface
Minimum
0
Default
0
Type
1 Bit Volatile
Display Format
None
Coding
RW, NC
If the host drive is defaulted (see the drive user guide for details), it will also clear the current configuration for the slot the module is installed to.
This can be performed as follows:
Set Pr S.01.002 to On.
Reset the module by setting Pr S.01.001 to On.
Default parameter values for the module will be loaded.
The module will reset using the default values.
S.01.004
Option Module Status
Minimum
0
Default
Type
8 Bit Volatile
Display Format
None
Coding
RO, TE, ND, NC, PT
This parameter displays the current status of the module. All possible values are shown in the table below.
Value
Text
0
Running OK
The module is healthy.
1
Initializing
Indicates that the module is initializing.
Indicates that there is an error in the mapping parameters.
2
Mapping Error
For example, the destination should not be non-existent or
read-only.
An error has occurred preventing the firmware or user
3
Error
program from running correctly.
100
Bootloader
The bootloader is currently running.
The bootloader is currently performing a firmware update.
101
Updating
The power must not be turned off in this state.
18
Mechanical
Electrical
Single line
installation
installation
descriptions
Maximum
1
Units
Update Rate
Read every 200 ms
Decimal Places
0
Maximum
1
Units
Update Rate
Read every 200 ms
Decimal Places
0
Maximum
2
Units
Update Rate
Background read
Decimal Places
0
Description
Parameters
Block diagrams
Diagnostics
Technical Data
Index
SI-I/O User Guide
Issue Number: 3

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

0478-0047-03

Table of Contents