I/O Output Enable Register
0 (Display
Minimum
0000000000)
Default
0
Type
16 Bit User Save
Display Format
Binary
Coding
RW
Parameter S.01.005 is used to disable or enable relevant bits in the Output Register (Pr S.01.007).
If the bit is set to zero, the relevant bit in the Output Register (Pr S.01.007) is disabled. If the bit is set to 1 then the relevant bit in the Output Register
can be used to directly control the digital output but the conditions below will need to be fulfilled:
The corresponding bit in the I/O Output Enable Register (Pr S.01.005) is set to 1.
The I/O must be a digital I/O and configured as an output or is a Relay Output.
The corresponding I/O Source/Destination parameter must be set to 00.000.
If the above conditions are not met, then the digital output is controlled by the normal logic.
The table below shows how the bits correspond to each function.
Bit
9
8
7
Terminal
T23
T21
T11
Relay
Relay
Digital
Terminal
2
1
Input
description
8
S.01.006
I/O Input Register
0 (Display
Minimum
00000000)
Default
0
Type
16 Bit Volatile
Display Format
Binary
Coding
RO
The Digital I/O Input Register (Pr S.01.006) is always active and displays the state of all the digital I/O which are configured as inputs.
This register is updated every 1 ms.
The table below shows how the bits correspond to each function.
Bit
7
6
Terminal
T11
T9
Terminal
Digital
Digital
description
Input 8
Input 7
S.01.007
I/O Output Register
0 (Display
Minimum
0000000000)
Default
0
Type
16 Bit User Save
Display Format
Binary
Coding
RW
Bits in the I/O Output Register (Pr S.01.007) can be used to control the digital I/O directly. The bits control the output directly and are not modified by
the corresponding Digital I/O Invert function. The bits in the I/O Output Register (Pr S.01.007) only control the corresponding digital output if all the
conditions below are met:
The corresponding bit in the I/O Output Enable Register (Pr S.01.005) is set to 1.
The I/O must be a digital I/O and configured as an output or is a Relay Output.
The corresponding I/O Source/Destination parameter must be set to 00.000.
If the above conditions are not met, then the digital output is controlled by the normal logic.
The table below shows how the bits correspond to each function.
Bit
9
8
Terminal
T23
T21
Relay
Relay
Digital
Terminal
2
1
Input
description
SI-I/O User Guide
Issue Number: 3
Mechanical
Electrical
installation
installation
Maximum
Units
Update Rate
Decimal Places
6
5
4
3
T9
T8
T7
T5
Digital
Digital
Digital
Digital
Input
Input
Input
I/O 4
7
6
5
Maximum
Units
Update Rate
Decimal Places
5
4
3
T8
T7
T5
Digital
Digital
Digital
Digital
Input 6
Input 5
I/O 4
Maximum
Units
Update Rate
Decimal Places
7
6
5
4
T11
T9
T8
T7
T5
Digital
Digital
Digital
Digital
Input
Input
Input
I/O 4
8
7
6
5
Single line
Parameters
Block diagrams
descriptions
1023 (Display
1111111111)
Background read
0
2
1
0
T4
T3
T2
Digital
Digital
Digital
I/O 3
I/O 2
I/O 1
255 (Display
11111111)
1 ms write
0
2
1
0
T4
T3
T2
Digital
Digital
I/O 3
I/O 2
I/O 1
1023 (Display
1111111111)
2 ms read
0
3
2
1
0
T4
T3
T2
Digital
Digital
Digital
I/O 3
I/O 2
I/O 1
Diagnostics
Technical Data
Index
19

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

0478-0047-03

Table of Contents