Menu 2 - Digital I/O

Menu 2 on the module controls and displays all parameters associated with the Digital I/O.
S.02.001
Digital I/O 1 State
S.02.002
Digital I/O 2 State
S.02.003
Digital I/O 3 State
S.02.004
Digital I/O 4 State
S.02.005
Digital Input 5 State
S.02.006
Digital Input 6 State
S.02.007
Digital Input 7 State
S.02.008
Digital Input 8 State
S.02.009
Relay 1 State
S.02.010
Relay 2 State
Minimum
0
Default
0
Type
1 Bit Volatile
Display Format
None
Coding
RO, ND, ND, PT
Digital I/O X State shows the state of the digital I/O in question. All I/O use IEC61131-2 logic levels. As default the inputs use positive logic, and so the
state parameter is 0 if the digital I/O is low or 1 if the digital I/O is high. Digital I/O Logic Polarity (Pr S.01.008) can be set to Negative Logic (0) to
change the logic for Digital I/O 1-8, so that the state parameter is 0 if the digital I/O is high and 1 if the digital I/O is low.
The state parameter represents the digital I/O state whether it is configured as an input or as an output. If the digital I/O is configured as an output to
be controlled using the Digital I/O Register (Pr S.01.007), then the state parameter will still show the state of the output even though the source is
zero.
For Relay 1 and 2, the state parameter is 0 if the relay contact is open, the state parameter is 1 if the relay contact is closed.
S.02.011
Digital I/O 1 Invert
S.02.012
Digital I/O 2 Invert
S.02.013
Digital I/O 3 Invert
S.02.014
Digital I/O 4 Invert
S.02.015
Digital Input 5 Invert
S.02.016
Digital Input 6 Invert
S.02.017
Digital Input 7 Invert
S.02.018
Digital Input 8 Invert
S.02.019
Relay 1 Invert
S.02.020
Relay 2 Invert
Minimum
0
Default
0
Type
1 Bit User Save
Display Format
None
Coding
RW
A value of Off (0) or On (1) in Digital I/O X Invert allows the I/O state to be non-inverted or inverted as required.
S.02.021
Digital I/O 1 Source / Destination
S.02.022
Digital I/O 2 Source / Destination
S.02.023
Digital I/O 3 Source / Destination
S.02.024
Digital I/O 4 Source / Destination
S.02.025
Digital Input 5 Destination
S.02.026
Digital Input 6 Destination
S.02.027
Digital Input 7 Destination
S.02.028
Digital Input 8 Destination
S.02.029
Relay 1 Source
S.02.030
Relay 2 Source
Minimum
0.00.000
Default
0.00.000
Type
32 Bit User Save
Display Format
Slot Menu Parameter Decimal Places
Coding
RW, PT, BU
The Digital I/O X Source / Destination parameters provide the routing for the source and/or destination for the digital I/O.Relay X Source provides the
routing for the source of the two relays.
SI-I/O User Guide
Issue Number: 3
Mechanical
Electrical
Single line
installation
installation
descriptions
Maximum
1
Units
2 ms read/write - Unidrive M600 - M800
Update Rate
8 ms read/write - Unidrive M200 - M400
Decimal Places
0
Maximum
1
Units
Update Rate
Background read
Decimal Places
0
Maximum
4.99.999
Units
Update Rate
Drive Reset read
0
Parameters
Block diagrams
Diagnostics
Technical Data
Index