DeviceNetstart-up
Name
Address of data attribute
of the assemblies for
read access.
Class, instance, attributes
PV+P1+P2+
4, 6, 3
MTMP+ERR
PV+SP+CMD+
4, 7, 3
P1+P2+
MTMP+ERR
Typ 8750
Format of the data
attribute
Byte 0: PV low
Byte 1: PV high
Byte 2: P1 low
Byte 3: P1 high
Byte 4: P2 low
Byte 5: P2 high
Byte 6: MTMP low
Byte 7: MTMP high
Byte 8: ERR
Byte 0: PV low
Byte 1: PV high
Byte 2: SP low
Byte 3: SP high
Byte 4: CMD low
Byte 5: CMD high
Byte 6: P1 low
Byte 7: P1 high
Byte 8: P2 low
Byte 9: P2 high
Byte 10: MTMP low
Byte 11: MTMP high
Byte 12: ERR
Name
Address of data attribute
of the assemblies for
read access.
Class, instance, attributes
PV+POS+
4, 8, 3
ERR+PCON
PV+POS+
4, 9, 3
ERR+
PCON+
P1
Tab. 26: Static Input Assemblies, DeviceNet
The addresses indicated in "Tab. 26" can be used as a path
statement for the Produced Connection Path attribute of an
I/O connection.
This I/O connection can be used to transfer the attributes described
in more detail in the following "Tab. 27" as input process data.
Nevertheless, by using this address data, the attributes combined
in the assemblies can also be accessed acyclically at any time via
Explicit Messages.
english
Format of the data
attribute
Byte 0: PV low
Byte 1: PV high
Byte 2: POS low
Byte 3: POS high
Byte 4: ERR
Byte 5: PCON
active
Byte 0: PV low
Byte 1: PV high
Byte 2: POS low
Byte 3: POS high
Byte 4: ERR
Byte 5: PCON active
Byte 6: P1 low
Byte 7: P2 low
45