Electricalinstallation
Circular plug M12, 8-pole
Set-point value, digital input
Pin
Wire color
4)
Assignment
8
red
Set-point value + (0/4 – 20 mA / 0 – 5/10 V)
7
blue
Set-point value GND
1
white
Digital input +
Input/output signals
Pin
Wire color
4)
Assignment
6
pink
Analog position feedback +
5
gray
Analog position feedback GND
4
yellow
Digital output 1
3
green
Digital output 2
2
brown
Digital outputs GND
Tab. 7:
Circular plug M12, 8-pole
Circular plug M8, 4-pole (pressure sensor)
Pin
Wire color
Assignment
1
brown
+ 24 V pressure sensor power supply
2
white
4 – 20 mA output from pressure sensor
Tab. 8:
Circular plug M8, 4-pole (pressure sensor)
Circular plug M12, 4-pole (operating voltage)
Pin
Wire color
5)
Assignment
1
brown
Operating voltage +
3
blue
Operating voltage
Tab. 9:
Circular plug M12, 4-pole (operating voltage)
Typ 8750
24 V DC
GND
10.2 Electrical installation PROFIBUS DP
Procedure:
Connect the process controller according to "Fig. 13" and "Tab.
10", "Tab. 11", "Tab. 12".
The electrical connection module of Type 8693 features a setscrew
with nut which is used to connect the Technical Earth (TE)
(see "Fig. 13: Connection with PROFIBUS DP").
Connect setscrew (TE connection) to a suitable grounding point.
To ensure electromagnetic compatibility (EMC), ensure that the
cable is as short as possible (max. 30 cm, Ø 1.5 mm
When the operating voltage is applied, the process controller is
operating.
Now make the required basic settings and actuate automatic
adjustment of the process controller, as described in
Chapter "13 PROFIBUS DP start-up", page 38.
The settings in the BUS.COMM menu option are described
in Chapter "13 PROFIBUS DP start-up".