Electricalinstallation
Circular plug M12, 8-pole
Set-point value, digital input
Pin
Wire color
4)
Assignment
8
red
Set-point value + (0/4 – 20 mA / 0 – 5/10 V)
7
blue
Set-point value GND
1
white
Digital input +
Input/output signals
Pin
Wire color
4)
Assignment
6
pink
Analog position feedback +
5
gray
Analog position feedback GND
4
yellow
Digital output 1
3
green
Digital output 2
2
brown
Digital outputs GND
Tab. 7:
Circular plug M12, 8-pole
Circular plug M8, 4-pole (pressure sensor)
Pin
Wire color
Assignment
1
brown
+ 24 V pressure sensor power supply
2
white
4 – 20 mA output from pressure sensor
Tab. 8:
Circular plug M8, 4-pole (pressure sensor)
Circular plug M12, 4-pole (operating voltage)
Pin
Wire color
5)
Assignment
1
brown
Operating voltage +
3
blue
Operating voltage
Tab. 9:
Circular plug M12, 4-pole (operating voltage)
Typ 8750
24 V DC
GND
10.2 Electrical installation PROFIBUS DP
Procedure:
→
Connect the process controller according to "Fig. 13" and "Tab.
10", "Tab. 11", "Tab. 12".
The electrical connection module of Type 8693 features a setscrew
with nut which is used to connect the Technical Earth (TE)
(see "Fig. 13: Connection with PROFIBUS DP").
→
Connect setscrew (TE connection) to a suitable grounding point.
To ensure electromagnetic compatibility (EMC), ensure that the
cable is as short as possible (max. 30 cm, Ø 1.5 mm
When the operating voltage is applied, the process controller is
operating.
→
Now make the required basic settings and actuate automatic
adjustment of the process controller, as described in
Chapter "13 PROFIBUS DP start-up", page 38.
The settings in the BUS.COMM menu option are described
in Chapter "13 PROFIBUS DP start-up".
english
2
).