Name
Description
PDI:POS
Actual position (position)
Actual value of positioner as ‰.
Value range 0 – 1000.
Values < 0 or > 1000 are
possible if e.g. X.TUNE has not
run through correctly.
PDI:CMD
Set-point position (command)
Set-point value of positioner
as ‰.
Value range 0 – 1000.
PDI:PV
Process actual value
(process value)
Actual value of process controller
in physical unit (as set in the menu
P.CO INP or P.CO SCAL),
max. value range -999 – 9999,
depending on internal scaling.
PDI:SP
Process set-point value (set-point)
Set-point value of process
controller in physical unit
(as set in the menu P.CO INP or
P.CO SCAL),
max. value range -999 – 9999,
depending on internal scaling.
40
Identifier
GSD file:
PDI:POS
Identifier (HEX):
41, 40, 00
GSD file:
PDI:CMD
Identifier (HEX):
41, 40, 01
GSD file:
PDI:PV
Identifier (HEX):
41, 40, 02
GSD file:
PDI:SP
Identifier (HEX):
41, 40, 03
english
Typ 8750
PROFIBUSDPstart-up
Name
Description
PDI:TEMP
Device temperature (temperature)
Temperature of 0.1 °C is
measured on the CPU board by
the sensor,
value range -550 (-55 °C) –
+1250 (+125 °C).
PDI:MODE Operating state (operation mode)
Operating state:
0: AUTO
1: MANUAL
2: XTUNE
9: P.QLIN
10: P.TUNE
12: BUSSAFEPOS
PDI:ERR
Error
Indicates the number of the
process value (output) which was
not written. The value is retained
until it is deleted with PDO:ERR.
HEX
14 PDO:CMD / SP
16 PDO:MODE
Identifier
GSD file:
PDI:TEMP
Identifier (HEX):
41, 40, 04
GSD file:
PDI:MODE
Identifier (HEX):
41, 00, 05
GSD file:
PDI: ERR
Identifier (HEX):
41, 00, 06