Devicenet Start-Up; Settings In Bus.comm - Burkert 8750 Quick Start Manual

Flow controller
Table of Contents

Advertisement

Name
Description
PDO:ERR
Reset error display
If the value > 0, ERR is reset.
PDO:
Medium temperature
MTMP
Temperature in °C on 1 °C exactly
Value range 0 °C – 150 °C
PDO:
0: Positioner
CONact
1: Process controller
Tab. 25: Process Data Output, PROFIBUS DP
42
Identifier
GSD file:
PDO: ERR
Identifier (HEX):
81, 00, 17
GSD file:
PDO:MTMP
Identifier (HEX):
81, 40, 18
GSD file:
PDO:CONact
Identifier (HEX):
81, 00, 19
english
Typ 8750
DeviceNetstart-up
14
DEVICENET START-UP
Procedure:
• Perform the automatic adjustment (X.TUNE) of the process controller.
• Add the F.CONTROL auxiliary function to the main menu using the
configuration menu (ADDFUNCTION) and create settings.
• Make settings in the BUS.COMM function.
• Configuration of the process values.
14.1 Settings in BUS.COMM
Enter a device address (value between 0 and 63)
Address X
Selection of the baud rate
BAUD RATE
• The baud rate can be changed either by pressing the operator keys
on the device or via the bus.
• A change has no effect until a reset (send a reset message to
the identity object) or power up is implemented. This means if the
changed baud rate attribute is accessed before a reset or power up,
the read (changed) value does not agree with the still current baud
rate (to be changed) of the network.
Select 125 kbit/s, 250 kbit/s or 500 kbit/s