3.4

List of Error Codes

The pulse input module stores an error code in a buffer memory area of the error channel when an error occurs during its
operation. In addition, the input signal (X) of the error channel listed below turns on.
To clear the error, turn on the output signal (Y) of the error channel listed below so that the error code stored in a buffer
memory area of the error channel is cleared. With this timing, the input signal (X) of the error channel listed below turns off.
The corresponding buffer memory area and I/O signals (X/Y) vary depending on the channel where an error has occurred.
Error channel
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
Error codes of the pulse input module are classified as minor errors or moderate errors.
• Minor error: An error that occurs due to failure of programs such as a fault in execution timing. Each function can be
performed normally after the error cause is eliminated by reviewing programs. (Number in the 1000s + H)
• Moderate error: An error such as a hardware failure. The count operation does not continue. (Number in the 3000s + H)
The following table lists the error codes to be stored.
 in error codes: For what this symbol indicates, refer to Description and cause.
Error code
Error name
0000H
*1*2
180H
Interrupt factor generation
setting range error
*1*2
181H
Condition target setting range
error
*1*2
182H
Condition target channel
setting range error
*3*4
1900H
Overflow error
*4*5
1920H
Preset setting value for
accumulating count value
setting error
*1
1940H
Comparison output selection
setting error
*1
1941H
Comparison output setting
value setting error
*1
1AA0H
Moving average processing
selection setting error
3 TROUBLESHOOTING
52
3.4 List of Error Codes
Buffer memory area
'CH1 Error code' (Un\G9)
'CH2 Error code' (Un\G25)
'CH3 Error code' (Un\G41)
'CH4 Error code' (Un\G57)
'CH5 Error code' (Un\G73)
'CH6 Error code' (Un\G89)
'CH7 Error code' (Un\G105)
'CH8 Error code' (Un\G121)
Description and cause
There is no error.
A value other than Interrupt resend request (0) and
No interrupt resend request (1) is set in Interrupt
factor generation setting [n].
 indicates the interrupt setting related to the error
as follows:
0: Setting 1 to F: Setting 16
A value other than Invalid (0) to Warning output flag
(5) has been set in Condition target setting [n].
 indicates the interrupt setting related to the error
as follows:
0: Setting 1 to F: Setting 16
A value other than All channels (0) to CH8 (8) has
been set in Condition target channel setting [n].
 indicates the interrupt setting related to the error
as follows:
0: Setting 1 to F: Setting 16
CH Accumulating count value exceeded
99999999 when the ring counter was selected.
A value other than 0 to 99999999 is set in CH
Preset setting value for accumulating count value.
A value other than Comparison output function
invalid (0) and Comparison output function valid (1)
is set in CH Comparison output selection.
A value other than 0 to 99999999 is set in CH
Comparison output setting value.
A value other than Sampling processing (0) and
Moving average processing (1) is set in CH
Moving average processing selection.
Input signal (X)
'CH1 Error occurrence' (X8)
'CH2 Error occurrence' (X9)
'CH3 Error occurrence' (XA)
'CH4 Error occurrence' (XB)
'CH5 Error occurrence' (XC)
'CH6 Error occurrence' (XD)
'CH7 Error occurrence' (XE)
'CH8 Error occurrence' (XF)
Action
Set Interrupt factor generation setting [n] to Interrupt
resend request (0) or No interrupt resend request
(1).
Set Condition target setting [n] to a value from
Invalid (0) to Warning output flag (5).
Set Condition target channel setting [n] to a value
from All channels (0) to CH8 (8).
Set CH Preset setting value for accumulating
count value to a value between 0 and 99999999,
and then set CH Counter reset request to Reset
request (1) to reset CH Accumulating count value.
(It is necessary to restart the count operation with
CH Counter reset request.)
Set CH Preset setting value for accumulating
count value to a value between 0 and 99999999,
and then set CH Counter reset request to Reset
request (1).
Set CH Comparison output selection to
Comparison output function invalid (0) or
Comparison output function valid (1).
Set CH Comparison output setting value to 0 to
99999999.
Set CH Moving average processing selection to
Sampling processing (0) or Moving average
processing (1).
Output signal (Y)
'CH1 Error reset request' (Y8)
'CH2 Error reset request' (Y9)
'CH3 Error reset request' (YA)
'CH4 Error reset request' (YB)
'CH5 Error reset request' (YC)
'CH6 Error reset request' (YD)
'CH7 Error reset request' (YE)
'CH8 Error reset request' (YF)