CH1 Preset setting value for accumulating count value
Set the value to preset the accumulating count value when resetting the accumulating count value.
■Buffer memory addresses
The following shows the buffer memory addresses of this area.
Buffer memory name
CH Preset setting value for accumulating count value
CH Preset setting value for accumulating count value
(when Q series-compatible mode is used)
■Setting range
• The setting range is from 0 to 99999999.
• For channels on which the set value is outside the setting range, a preset setting value for accumulating count value setting
error (error code: 1920H) occurs.
■Enabling the setting
Regardless of turning on and off 'Operating condition setting request flag' (Y1), the value becomes enabled when it is set.
■Default value
The default value is 0 for all channels.
CH1 Counter reset request
This area is used to reset the sampling pulse number, input pulse value, and accumulating count value.
For details on the counter reset function, refer to the following.
Page 31 Counter Reset Function
Setting value
0
1
Setting 'CH1 Counter reset request' (Un\G386) to Reset request (1) changes each count value as shown below.
• 'CH1 Sampling pulse number' (Un\G0) is reset to 0. After the reset is complete and 'CH1 Counter reset request' (Un\G386)
is set to No reset request (0), input pulses are invalid for a maximum of 20ms.
• 'CH1 Accumulating count value' (Un\G2, Un\G3) is reset to 0. If 'CH1 Preset setting value for accumulating count value'
(Un\G384, Un\G385) is set to a value other than 0, the accumulating count value is preset to the setting value.
• 'CH1 Input pulse value' (Un\G4, Un\G5) is reset to 0.
If a value other than Reset request (1) is set, the setting details are ignored.
■Buffer memory addresses
The following shows the buffer memory addresses of this area.
Buffer memory name
CH Counter reset request
CH Counter reset request (when Q series-compatible
mode is used)
■Default value
The default value is No reset request (0) for all channels.
APPX
86
Appendix 3 Buffer Memory Areas
CH1
CH2
CH3
384, 385
400, 401
416, 417
26, 27
58, 59
90, 91
Setting details
No reset request
(The setting value is automatically returned to 0 after the resetting of the
counter value is complete.)
Reset request
CH1
CH2
CH3
386
402
418
13
45
77
CH4
CH5
CH6
432, 433
448, 449
464, 465
122, 123
154, 155
186, 187
CH4
CH5
CH6
434
450
466
109
141
173
CH7
CH8
480, 481
496, 497
218, 219
250, 251
CH7
CH8
482
498
205
237