1.4

Pre-scale Function

This function converts the pulse number by multiplying the input pulse number by an arbitrary setting value.
Sampling pulse number calculation
The following arithmetic expression is used to convert the input pulse value per count cycle into a unit pulse number. The
converted value is stored in 'CH1 Sampling pulse number' (Un\G0) as the sampling pulse number.
Input pulse
Number of
=
value per count
sampling pulses
cycle
Values after the decimal point are omitted.
■Pre-scale setting value
Set this with 'CH1 Pre-scale setting value' (Un\G135). The setting range is from 0 to 32767.
■Unit scaling
Set this with 'CH1 Pre-scale function selection' (Un\G134).
Setting value
0
1
2
3
4
5
'CH1 Pre-scale function selection' (Un\G134) is also used to set whether to use the pre-scale function. To use the pre-scale
function, select a value other than Pre-scale function invalid (0).
Pre-scale setting
×
×
Unit magnification
value
Setting details
Pre-scale function invalid
1
0.1
0.01
0.001
0.0001
1 FUNCTIONS
23
1.4 Pre-scale Function
1