CH1 Pre-scale function selection
Set whether to use the pre-scale function. When using this function, also set the unit scaling to use in calculating the sampling
pulse number.
The sampling pulse number is calculated with the following arithmetic expression. Values after the decimal point are omitted.
Input pulse
Number of
=
value per
sampling pulses
count cycle
For details on the pre-scale function, refer to the following.
Page 23 Pre-scale Function
Setting value
0
1
2
3
4
5
• If a value other than those shown in the above table is set, a pre-scale function selection setting error (error code: 1AB0H)
occurs.
• When 'CH1 Movement averaging processing selection' (Un\G132) is set to Moving average processing (1), moving
average processing is performed on the sampling pulse number for the number of operations set by 'CH1 Number of
movement averaging processing' (Un\G133).
■Buffer memory addresses
The following shows the buffer memory addresses of this area.
Buffer memory name
CH Pre-scale function selection
CH Pre-scale function selection (when Q series-
compatible mode is used)
■Enabling the setting
Turn on and off 'Operating condition setting request flag' (Y1).
■Default value
The default value is Pre-scale function invalid (0) for all channels.
Pre-scale setting
×
×
value
CH1
CH2
134
166
6
38
Unit magnification
Setting details
Pre-scale function invalid
1
0.1
0.01
0.001
0.0001
CH3
CH4
CH5
198
230
262
70
102
134
Appendix 3 Buffer Memory Areas
CH6
CH7
CH8
294
326
358
166
198
230
APPX
A
81