Iologik E1213 Modbus Address And Register Map - Moxa Technologies ioLogik E1211 User Manual

Iologik e1200 series
Hide thumbs Also See for ioLogik E1211:
Table of Contents

Advertisement

ioLogik E1200 Series
ioLogik E1213 Modbus Address and Register
Map
I/O
Parameter Name
DI_counterOverflowFl
ag
DI_counterOverflowFl
agClear
DI_counterReset
DI_counterStatus
DI_counterValue
DI_status
DI-all_statusFromDI-
00
DO_p2pSafeModeFla
gClear
DO_p2pSafeModeFla
g
DO_p2pStatus
DO_pulseCount
DO_pulseOffWidth
DO_pulseOnWidth
DO_pulseStatus
DO_status
DO-all_statusFromDO
-00
Description
Start
Address
(decimal)
0: Normal, 1:
1000
Overflow
1: clear
0288
overflow flag
1: reset to
0272
initial value
0: STOP, 1:
0256
START
high/low word 0016
0: OFF, 1: ON
0000
0: OFF, 1: ON
0048
1: clear safe
4128
mode flag
0: OFF, 1: ON
4112
0: OFF, 1: ON
4096
0036
unit: 1 ms
0068
unit: 1 ms
0052
0: STOP, 1:
0016
START
0: OFF, 1: ON
0000
0: OFF, 1: ON
0032
A-7
Modbus/TCP Default Address Mappings
Point
Start
Type
Register
(decimal)
02:INPUT
11001
STATUS
01:COIL
00289
STATUS
01:COIL
00273
STATUS
01:COIL
00257
STATUS
04:INPUT
30017
REGISTER
02:INPUT
10001
STATUS
04:INPUT
30049
REGISTER
01:COIL
04129
STATUS
02:INPUT
14113
STATUS
02:INPUT
14097
STATUS
03:HOLDI
40037
NG
REGISTER
03:HOLDI
40069
NG
REGISTER
03:HOLDI
40053
NG
REGISTER
01:COIL
00017
STATUS
01:COIL
00001
STATUS
03:HOLDI
40033
NG
REGISTER
Length
Access
Type
12
R
bit
12
R/W
bit
12
R/W
bit
12
R/W
bit
24
R
2 words
12
R
bit
1
R
word
8
R/W
bit
8
R
bit
8
R
bit
8
R/W
word
8
R/W
word
8
R/W
word
8
R/W
bit
8
R/W
bit
1
R/W
word

Hide quick links: