Ethernet/Ip Default Address Mappings - Moxa Technologies ioLogik E1211 User Manual

Iologik e1200 series
Hide thumbs Also See for ioLogik E1211:
Table of Contents

Advertisement

ioLogik E1200 Series
DO Channel Object (0x67)
Instance
Attribute ID
0x00
0x01
0x64
0x01
0x64
0x02
0x64
0x03
0x64
0x04
0x64
0x05
0x64
0x06
0x64
0x07
Relay Channel Object (0x6A)
Instance
Attribute ID
0x00
0x01
0x64
0x01
0x64
0x02
0x64
0x03
0x64
0x04
0x64
0x05
0x64
0x06
0x64
0x07
0x64
0x08
0x64
0x09
0x64
0x0A
AI Channel Object (0x6B)
Instance
Attribute ID
0x00
0x01
0x64
0x01
0x64
0x02
0x64
0x03
0x64
0x04
0x64
0x05
0x64
0x06
0x64
0x07
0x64
0x08
0x64
0x09
0x64
0x0A
0x64
0x0B
0x64
0x0C
Access
Name
GET
Revision
GET
doIndex
GET
doMode
SET
doStatus
SET
doPulseStatus
SET
doPulseCount
SET
doPulseOnWidth
SET
doPulseOffWidth
Access
Name
GET
Revision
GET
relayIndex
GET
relayMode
SET
relayStatus
SET
relayPulseStatus
SET
relayPulseCount
SET
relayPulseOnWidth
SET
relayPulseOffWidth
GET
relayTotalCount
GET
relayCurrentCount
SET
relayCurrentCount
Reset
Access
Name
GET
Revision
GET
aiIndex
GET
aiMode
GET
aiValueRaw
GET
aiValueScaled
GET
aiValueRawMin
GET
aiValueRawMax
GET
aiValueScaledMin
GET
aiValueScaledMax
SET
aiResetMinValue
SET
aiResetMaxValue
GET
aiStatus
GET
aiBurnoutValue
B-3

EtherNet/IP Default Address Mappings

Data Type
Description
UINT
class revision
UINT
DO - index
BOOL
DO - mode (0: DO, 1: Pulse)
BOOL
DO - DO mode - status (0: OFF, 1:
ON)
BOOL
DO - Pulse mode - status (0: STOP,
1: START)
UINT
DO - Pulse mode - count
UINT
DO - Pulse mode - ON width (unit:
1 ms)
UINT
DO - Pulse mode - OFF width (unit:
1 ms)
Data Type
Description
UINT
class revision
UINT
Relay - index
BOOL
Relay - mode (0: Relay, 1: Pulse)
BOOL
Relay - Relay mode - status (0:
OFF, 1: ON)
BOOL
Relay - Pulse mode - status (0:
STOP, 1: START)
UINT
Relay - Pulse mode - count
UINT
Relay - Pulse mode - ON width
(unit: 1.5 s)
UINT
Relay - Pulse mode - OFF width
(unit: 1.5 s)
UDINT
Relay - Relay mode - total count
UDINT
Relay - Relay mode - current count
BOOL
Relay - Relay mode - reset current
count (1: RESET)
Data Type
Description
UINT
class revision
UINT
AI - index
UINT
AI - mode (0: 0-10 V, 1: 4-20 mA,
2: 0-20 mA, 4: 4-20 mA burnout)
UINT
AI - raw value
REAL
AI - scaled value
UINT
AI - minimum raw value
UINT
AI - maximum raw value
REAL
AI - minimum scaled value
REAL
AI - maximum scaled value
BOOL
AI - reset minimum value (1:
RESET)
BOOL
AI - reset maximum value (1:
RESET)
UINT
AI - status (0: normal, 1: burnout,
2: over range, 3. under range)
REAL
AI - burnout value