Factory Default Settings - Moxa Technologies ioLogik E1211 User Manual

Iologik e1200 series
Hide thumbs Also See for ioLogik E1211:
Table of Contents

Advertisement

ioLogik E1200 series products are configured with the following factory default settings:
Default IP address
Default Netmask
Default Gateway
Communication watchdog
Modbus/TCP Alive Check
Modbus/TCP Timeout Interval
DI Mode
Filter time
Trigger for counter
Counter status
DO Mode
DO Safe Status
Power on status
Low width for pulse
Hi width for pulse
Output pulses
DIO Mode
AI Mode
Scaling and Slop-Intercept
Password
Server Name
Server Location
AO Mode
Scaling

Factory Default Settings

E.
192.168.127.254
255.255.255.0
0.0.0.0
Disable
On
60 sec
DI
100 ms
Lo to Hi
Stop
DO
Disable
Disable
1 ms (1.5 s for relay)
1 ms (1.5 s for relay)
0 (continuous)
DO
Voltage
Disable
N/A
N/A
N/A
Voltage
Disable
E