AOPC Server Settings

Moxa's MX-AOPC Server™ is a software package operated as an OPC driver of an HMI or SCADA system. It
seamlessly connects Moxa's ioLogik products to a wide variety of SCADA systems, including the most popular:
Wonderware, Citect, and iFix. MX-AOPC UA Server™ conforms to the OPC UA standard to connect with other
standards-compliant devices and host OPC machines.
Hardware Requirements
CPU
RAM
Communication Interface
Software Requirements
Operating System
Editor (optional)
Database (optional)
OPC UA Server Specifications
OPC Unified Architecture
OPC Data Access
Device Protocols
OPC UA Logger Specifications
OPC Unified Architecture
MX-AOPC UA Server can be downloaded from Moxa's website support page at www.moxa.com/support/.
After downloading the MX-AOPC UA Server file, unzip the file and run Install.exe. The installation program will
guide you through the installation process and install the MX-AOPC UA Server Utility.
For more details on MX-AOPC UA Server installation and use, please check the user's manual, which can be
downloaded from Moxa's website.

Tag Generation

Use the web console to create AOPC tags for the ioLogik E1200 by opening your browser and navigating to the
AOPC Server Settings page.
Follow these steps to create the tags and send them from the ioLogik E1200 to MX-AOPC UA Server:
1. On the AOPC & I/O Settings page, select the Enable Active OPC checkbox and specify the IP address
where the MX-AOPC UA Server is installed.
2. Select the I/O channels that need to be created in MX-AOPC UA Server.
3. Configure the Heartbeat Interval, if necessary.
NOTE
The Heartbeat Interval can be used to determine the connection status between the ioLogik E1200 and
MX-AOPC UA Server, and to ensure that the ioLogik is connected and alive. If the heartbeat interval is set and
the network between the ioLogik E1200 and MX-AOPC UA Server is down, MX-AOPC UA Server will detect the
stopped heartbeat and the Quality column in the MX-AOPC UA will display BAD to indicate the loss of
connectivity.
Intel Pentium 4 or above
512 MB (1024 MB recommended)
Ethernet or serial
Microsoft Windows 7/8/10, Microsoft Windows Server 2003/2008/2012
Microsoft Office 2003 (Access or Excel) or later
Oracle database, Microsoft SQL Server
1.01
1.0a, 2.0, 2.05a, 3.0
Moxa AOPC, Modbus/TCP (master), Modbus/RTU (master)
1.01
3-6
Using the Web Console