Lights Parameters; Current Limits Parameters - Curtis enAble 40 Manual

Powerchair control system
Table of Contents

Advertisement

PARAMETER
Running Lights
Running Light Volts
Min Light Current
*
Indicators
Indicator Volts
Min Indicator Current
*
Indicator Timeout
*
To set these minimum driver currents accurately, base your calculations
on the monitored values for Running Light Current and Indicator Current
as displayed in the programmer's Monitor menu.
PARAMETER
Peak Current Limit
Peak Current Time
Drive Current Limit
Brake Current Limit
*
The current limit range maxes out at 50 A for 50-amp controllers.
Curtis enAble
40 Manual,
®
5 — PROGRAMMABLE PARAMETERS:
LIGHTS MENU
RANGE
On/Off
Set to On if the vehicle has running rights.
12–24 V
Defines the voltage for the running lights. Bulbs will be held
at a constant brightness.
0–26.5 A
Defines the minimum allowed driver current for the running lights;
below this current, a fault will be declared.
On/Off
Set to On if the vehicle has indicator lights.
12–24 V
Defines the voltage for the indicator lights. Bulbs will be held
at a constant brightness.
0–26.5 A
Defines the minimum allowed driver current for the indicator lights;
below this current, a fault will be declared.
0–30 sec
Sets the maximum amount of time an indicator light will flash before
auto-shutdown. Setting this parameter to 0 disables this function.
CURRENT LIMITS MENU
RANGE
25–75 A
*
Provides a boost. Sets the motor current limit that will be allowed
for the peak current time.
0–20 sec
Sets the maximum time that the peak current is allowed.
25–60 A
*
Sets the motor current limit during normal driving.
25–60 A
*
Sets the motor current limit during regen braking.
Rev. E
Lights and Current Limits Parameters
DESCRIPTION
DESCRIPTION
29