Danfoss VLT AutomationDrive FC 360 Quick Manual page 9

Hide thumbs Also See for VLT AutomationDrive FC 360:
Table of Contents

Advertisement

Quick Start
Application
FC 360
Local/Remote
+24V 12
Description
DI1
For applications
where the speed
DI2
reference can be
DI3
switched between
DI4
local potentiometer
DI5
and remote current
DI6
signal
DI7
COM 20
+10V 50
AI1
AI2
COM 55
AO1
AO2
R1
R2
Parameter settings Setup 1
0-10 (Active Set-
[9] Multi Set-up
up)
0-12 (Link Set-up)
[20] Linked
1-00 (Configuration
[0] Speed Open Loop [0] Speed Open Loop
Mode)
3-00 (Ref Range)
[0] Min- Max
3-15 (Ref Source 1) [1] AI 53
3-16 (Ref Source 2)
4-12 (Motor Low
25.0 Hz
Limit)
4-14 (Motor High
50.0 Hz
Limit)
5-10 (DI 18
[8] Start
Selection)
5-12 (DI 27
[2] Coast Inverse
Selection)
5-14 (DI 32
[23] Set-up select
Selection)
5-40 (Relay 1
Running
Selection)
5-40 (Relay 2
Alarm
Selection)
6-10 (AI 53 Low)
0.07 V
6-11 (AI 53 High)
10 V
6-19 (AI 53 Mode)
[1] Voltage Mode
6-22 (AI 54 Low)
6-23 (AI 54 High)
6-29 (AI 54 Mode)
6-70 (Term 45
[0] 0-20 mA
Mode)
®
VLT
AutomationDrive FC 360 Quick Guide
18
Start
19
27
Coast inverse
29
32
Setup select
33
31
53
4-20
54
mA
-
+
45
42
1
2
3
4
5
6
Setup 2
[9] Multi Set-up
[20] Linked
[0] Min- Max
[2] AI 54
25.0 Hz
50.0 Hz
[8] Start
[2] Coast Inverse
[23] Set-up select
Running
Alarm
4.0 mA
20.0 mA
[0] Current Mode
[0] 0-20 mA
®
MG06A302 - VLT
is a registered Danfoss trademark
6-71 (AO45)
[100] Output freq
6-90 (Term 42
[0] 0-20 mA
Mode)
6-91 (AO42)
[103] Motor current
Table 1.4 [2] Local/Remote
Application
Conveyors, extruders
+24V 12
Description
DI1
For running at a stable
DI2
speed by a voltage
reference signal.
DI3
DI4
DI5
DI6
DI7
COM 20
+10V 50
AI1
AI2
COM 55
AO1
AO2
R1
R2
Parameter settings
1-00 (Configuration Mode): [0] Speed Open Loop
3-00 (Ref Range): [0] Min- Max
3-15 (Ref Source 1): [1] AI 53
4-12 (Motor Low Limit): 25.0 Hz
4-14 (Motor High Limit): 50.0 Hz
5-10 (DI 18 Selection): [8] Start
5-12 (DI 27 Selection): [2] Coast Inverse
5-40 (Relay 1 Selection): Running
5-40 (Relay 2 Selection): Alarm
6-10 (AI 53 Low): 0.07 V
6-11 (AI 53 High): 10 V
6-19 (AI 53 Mode): [1] Voltage Mode
6-70 (Term 45 Mode): [0] 0-20 mA
6-71 (AO45): [100] Output freq
6-90 (Term 42 Mode): [0] 0-20 mA
6-91 (AO42): [103] Motor current
Table 1.5 [3] Speed Open Loop
[100] Output freq
[0] 0-20 mA
[103] Motor current
FC 360
18
Start
19
27
Coast inverse
29
32
33
31
53
54
45
42
1
2
3
4
5
6
5
1
1

Advertisement

Table of Contents
loading

Table of Contents