Danfoss VLT AutomationDrive FC 360 Quick Manual page 39

Hide thumbs Also See for VLT AutomationDrive FC 360:
Table of Contents

Advertisement

Basic Troubleshooting and F...
Symptom
Phase to phase short
Open power fuses or circuit
breaker trip
Motor overload
Loose connections
Problem with mains power (See
Alarm 4 Mains phase loss
Mains current imbalance
description)
greater than 3%
Problem with the frequency
converter unit
Problem with motor or motor
wiring
Motor current imbalance
greater than 3%
Problem with the drive unit
Acoustic noise or vibration
(e.g. a fan blade is making
Resonances, e.g. in the motor/fan
noise or vibrations at
system
certain frequencies)
Table 7.1 Troubleshooting
®
VLT
AutomationDrive FC 360 Quick Guide
Possible Cause
Motor or panel has a short phase
to phase. Check motor and panel
phase for shorts.
Motor is overloaded for the
application.
Perform pre-startup check for loose
connections.
Rotate input power leads into the
drive one position: A to B, B to C, C
to A.
Rotate input power leads into the
frequency converter one position: A
to B, B to C, C to A.
Rotate output motor leads one
position: U to V, V to W, W to U.
Rotate output motor leads one
position: U to V, V to W, W to U.
Bypass critical frequencies by using
parameters in parameter group
4-6* Speed Bypass.
Turn off over-modulation in
14-03 Overmodulation.
Change switching pattern and
frequency in parameter group
14-0* Inverter Switching.
Increase Resonance Dampening in
1-64 Resonance Dampening.
®
MG06A302 - VLT
is a registered Danfoss trademark
Test
Eliminate any shorts detected.
Perform startup test and verify
motor current is within specifi-
cations. If motor current is
exceeding nameplate full load
current, motor may run only with
reduced load. Review the specifi-
cations for the application.
Tighten loose connections.
If imbalanced leg follows the wire,
it is a power problem. Check mains
power supply.
If imbalance leg stays on same
input terminal, it is a problem with
the unit. Contact the supplier.
If imbalanced leg follows the wire,
the problem is in the motor or
motor wiring. Check motor and
motor wiring.
If imbalance leg stays on same
output terminal, it is a problem
with the unit. Contact the supplier.
Check if noise and/or vibration
have been reduced to an
acceptable limit.
Solution
7
35
7