Specifications
Surroundings
Enclosure type J1-J7
Vibration test all enclosure types
Relative humidity
Aggressive environment (IEC 60068-2-43) H
Test method according to IEC 60068-2-43 H2S (10 days)
Ambient temperature (at 60 AVM switching mode)
- with derating
- at full continuous output current with some power size
- at full continuous output current
Minimum ambient temperature during full-scale operation
Minimum ambient temperature at reduced performance
Temperature during storage/transport
Maximum altitude above sea level without derating
Maximum altitude above sea level with derating
EMC standards, Emission
EMC standards, Immunity
Control card performance
Scan interval
Protection and features
Electronic thermal motor protection against overload.
Temperature monitoring of the heatsink ensures that the frequency converter trips if the temperature reaches a
predefined level. An overload temperature cannot be reset until the temperature of the heatsink is below the
temperature limit. For details of these limits and level, refer to the VLT
frequency converter has an auto derating function to avoid its heatsink reaching 95 °C.
The frequency converter is protected against short-circuits on motor terminals U, V, W.
If a mains phase is missing, the frequency converter trips or issues a warning (depending on the load and
parameter setting).
Monitoring of the intermediate circuit voltage ensures that the frequency converter trips if the intermediate circuit
voltage is too low or too high.
The frequency converter is protected against earth faults on motor terminals U, V, W.
®
VLT
AutomationDrive FC 360 Quick Guide
5-95% (IEC 721-3-3; Class 3K3 (non-condensing) during operation
S test
2
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
®
MG06A302 - VLT
is a registered Danfoss trademark
EN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3
EN 61800-3, EN 61000-6-1/2,
®
AutomationDrive FC 360 Design Guide. The
IP20, IP21/Type 1
1.0 g
class Kd
max. 55 °C
1)
max. 50 °C
1)
max. 45 °C
1)
0 °C
- 10 °C
-25 to +65/70 °C
1000 m
3000 m
1 ms
8
41
8