105 Drive Load

Parameter 105, the Drive Load parameter, shows the percentage torque of the drive when operating below
the knee frequency. It displays Load Torque if the frequency is below FKNEE, and displays Power if above
FKNEE.
The output current is measured with the motor power factor applied to an accuracy of ±20%.. The parameter
value is positive when the motor is pulling a load ("motoring mode") and negative when being pulled by a
load ("regenerative mode").

106 Load Torque

Parameter 106, the Load Torque parameter, displays the load torque of the drive.

107 Drive Temp

Parameter 107, the Drive Temp parameter, shows the actual temperature of the drive's heatsink. The drive
will fault when the internal temperature reaches 85°C
108 Total Run Time
Parameter 108, Total Run Time, is a resettable timer for drive operation. To reset the timer, enter 10 in
parameter 801, Program Number.
109 Power On Hours
Parameter 109, Power On Hours, displays how long the drive has been powered up.
110 Stator Freq
Parameter 110, Stator Frequency, displays the frequency the drive is applying to the motor stator.

111 DC Bus Voltage

Parameter 111, DC Bus Voltage, displays the voltage on the DC bus.
115 Drive Power Out
This parameter displays the power being output by the drive in terms of drive rating. The measurement is
calculated by scaling the Load Torque value by the ratio of Volt-Amps to Rated Volt-Amps, and adjusted by
Output Frequency.
116 Out Power (kW)
This parameter displays the average instantaneous power being output by the drive, in kW.
117 MWh Meter
This parameter displays megawatt hours of accumulated power consumption.
118 kWh Meter
This parameter displays kilowatt hours of accumulated power consumption.
120 Today's Date
This parameter displays today's date for customer access.
121 Today's Time
This parameter displays today's time for customer access.
7
vacon
vacon 500x parameters
Range: -200.0% to 200.0%
Read-Only
Range: -200.0%-200.0%
Read-Only
Range: -20.0 to 200.0 °C
Read-Only
.
Range: 0.0 - 6553.5 h
Read-Only
Range: 0 - 65535 h
Read-only
Range: 0.0-400.0 Hz
Read-only
Range: 0-1000 Vdc
Read-only
Range: 0.0%-200.0%
Read-only
Range: 0.0 - 327.67 kW
Read-only
Range: 0-32767 MWh
Read-only
Range: 0.0-999.9 kWh
Read-only
Range: MM/dd/YY
Read-Only
Range: 00:00 - 23:59
Read-Only