217 Trim Ref Enable
This parameter enables or disables trimming of the drive reference by an analog input and selects which
analog input will perform the trimming function.
Speed Reference = Main reference + (Trim % Factor) * (Analog in Percentage) * Max Frequency / 100%
Parameter Value
Disabled
Vin1
Vin2
Cin
Fxd Trim %
Note that setting a parameter for a Bipolar input value allows trimming both positive and negative around the
reference value.
218 Trim % Factor
This parameter determines the percentage of the analog input signal selected in
Enable, that will affect the reference signal.

301 Min Frequency

Parameter 301, Minimum Frequency, configures the minimum frequency output of the drive. This
parameter governs the minimum frequency when operating from the keypad or from an analog input. The
preset speeds can be set lower than the minimum frequency in parameter 301.

302 Max Frequency

Parameter 302, the Maximum Frequency parameter, configures the maximum frequency output of the
drive.
303 Preset Freq 1 (Jog Ref)
304

Preset Freq 2

Preset Freq 3
305
Preset Freq 4
306
Preset Freq 5
307
Preset Freq 6
308
310 Preset Freq 7
Preset Freq 8
311
Preset Freq 9
312
Preset Freq 10
313
314
Preset Freq 11
315
Preset Freq 12
Preset Freq 13
316
Preset Freq 14
317
Preset Freq 15
318
These parameters configure fifteen preset speeds in addition to the normal reference speed of the drive (as
defined by
set with
different speeds.
The speeds are selected by a combination of four digital inputs (PS1, PS2, PS3, PS4). A wiring scheme
for utilizing preset speeds is provided on page 36 along with a chart showing what combination of inputs
results in the selection of which speeds.
Note that parameter Parameter 303 (Preset Freq1) also serves as the reference frequency for jogging.
7
vacon
Description
No trimming of drive reference
Value of Vin1 will be used in the calculation above
Value of Vin2 will be used in the calculation above
Value of Cin will be used in the calculation above
Value of Fxd Trim % will be used
Drive Reference = Drive Reference + (Trim % Factor) * Max Frequency / 100% / 100%
parameters 201 (Input Mode)
parameter 302, Max Frequency).
vacon 500x parameters
Default = Disabled
Default = 0.0%
Default = 0.0%
Default: 60 Hz
Default: 5 Hz
Default: 10 Hz
Default: 20 Hz
Default: 30 Hz
Default: 40 Hz
Default: 50 Hz
Default: 60 Hz
Default: 0 Hz
Default: 2.5 Hz
Default: 7.5 Hz
Default: 15 Hz
Default: 25 Hz
Default: 35 Hz
Default: 45 Hz
Default: 55 Hz
and
204 (Ref Select)
and the maximum frequency of the drive (as
Thus, in effect, you may choose to operate the drive at up to 16
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
Range: n/a
Level: 2
Range: -100.0% to +100.0%
Level 2
Parameter 217, Trim Ref
Range: 0.0-Max Freq
Range: 0.0 to 400.0 Hz
Range: 0.0-Max Freq
Levels 1,2 for 303
Level 2 for 304-318