3. How to Install
Size/Type
P355
P400
P500
P560
3.9: E enclosures, 525-690 V
3
*170M fuses from Bussmann shown use the -/80 visual indicator; -TN/80 Type T, -/110 or TN/
110 Type T indicator fuses of the same size and amperage may be substituted for external use.
Danfoss PN
20220
20221
3.10: Additional Fuses for Non-UL Applications E enclosures, 525-690 V
Suitable for use on a circuit capable of delivering not more than 100,000 rms symmetrical amperes,
500/600/690 Volts maximum when protected by the above fuses.
Circuit Breaker Tables
Circuit Breakers manufactured by General Electric, Cat. No. SKHA36AT0800, 600 V AC maximum,
with the rating plugs listed below can be used to meet UL requirements.
Size/Type
P90
P110
P132
P160
P200
3.11: D enclosures, 380-500 V
Non-UL compliance
If UL/cUL is not to be complied with, we recommend using the following fuses, which will ensure
compliance with EN50178:
In case of malfunction, not following the recommendation may result in unnecessary damage to
the adjustable frequency drive.
P110 - P200
P250 - P400
62
Bussmann PN*
Danfoss PN
170M4017
20220
170M4017
20220
170M6013
20221
170M6013
20221
Bussmann
170M4017
170M6013
Rating plug catalog #
SRPK800A300
SRPK800A400
SRPK800A400
SRPK800A500
SRPK800A600
380-500 V
380-500 V
MG.33.U1.22 - VLT
®
Rating
Losses (W)
700 A, 700 V
700 A, 700 V
900 A, 700 V
900 A, 700 V
Ferraz
6.9URD31D08A0700
6.9URD33D08A0900
is a registered Danfoss trademark.
VLT
®
Automation Drive FC 300
Instruction Manual High Power
85
85
120
120
Siba
20 610 32.700
20 630 32.900
Amps
300
400
400
500
600
type gG
type gR