5. General Specifications
Max. Input Current [A]
Max. Input Current [A]
Max. external pre-fuses
[A]
Soft Charge Fuses
5
(qty)
SMPS fuse
AC Fan fuse
Supply Voltage [V]
Supply Frequency [Hz]
Power Factor
Efficiency
Power loss at rated max. load (400 V)
High Overload (150%) [W]
Normal Overload (110%) [W]
Enclosure
Vibration Test [g]
Relative Humidity [%]
Ambient
[degrees C]
Adjustable
Drive Protection
Weight
IP 00/ Chassis [kg]
IP 21/ NEMA 1 [kg]
IP 54/ NEMA 12 [kg]
1) Bussman 170M6000 series. See fuse chart.
2) Bussmann FWH-20A6F or exact equivalent, 3 per unit
3) Bussmann KTK-4 or exact equivalent, 1 per unit
4) Littlefuse KLK-15 or exact equivalent, 1 per unit
5) VLT with standard input option, no brake, no load sharing
120
VLT Type
400
460/ 500 436
1)
2)
AC [A]
3)
[A]
3)
[A]
Temperature
Frequency
5)
MG.33.U1.22 - VLT
380-500 Volt
P250
P315
472
590
590
647
531
531
580
700
900
20 (3)
4
4
3 Phase, 380-500 ± 10%
50/ 60
greater than 0.90
0.98
6005
6960
7630
7701
IP 00, IP 21/ NEMA 1 & IP 54/ NEMA 12
0.7
93%, +2%, -3% (IEC 68-2-3)
-10° C to 40° C [14°-104° F] continuously, periodi-
cally at +45° C [113° F]
-25° C to +65°/70° C [-13°-149°/158° F] for stor-
age/ transport
Ground and short-circuit protection
221.4
234.1
263.2
270.0
263.2
270.0
®
is a registered Danfoss trademark.
VLT
®
Automation Drive FC 300
Instruction Manual High Power
P355
P400
647
733
684
787
580
667
667
718
900
900
15
7691
7964
8879
9428
236.4
277.3
272.3
313.2
272.3
313.2