5. General Specifications
Max. Input Current [A]
Max. Input Current [A]
Max. external pre-fuses
Soft Charge Fuses
(qty)
5
SMPS fuse
AC Fan fuse
Supply Voltage [V]
Supply Frequency [Hz]
Power Factor
Efficiency
Power loss at rated max. load (400 V)
High Overload (150%) [W]
Normal Overload (110%) [W]
Enclosure
Vibration Test [g]
Relative Humidity [%]
Ambient Temperature [de-
grees C]
Adjustable Frequency Drive
Protection
Weight
IP 00/ Chassis [kg]
IP 21/ NEMA 1 [kg]
IP 54/ NEMA 12 [kg]
1) Bussman 170M6000 series. See fuse chart.
2) Bussmann FWH-20A6F or exact equivalent, 3 per unit
3) Bussmann KTK-4 or exact equivalent, 1 per unit
4) Littlefuse KLK-15 or exact equivalent, 1 per unit
5) VLT with standard input option, no brake, no load-share
118
VLT Type
460/ 500
1)
[A]
2)
AC [A]
3)
[A]
3)
[A]
5)
MG.33.U1.22 - VLT
380-500 Volt
P110
P132
400
204 251 251 304 304 381 381 463
183 231 231 291 291 348 348 427
350
400
3 Phase, 380-500 ± 10%
50/ 60
greater than 0.90
2995
3425
3782
4213
IP 00, IP 21/ NEMA 1 & IP 54/ NEMA 12
93%, +2%, -3% (IEC 68-2-3)
-10° C to 40° C [14°-104° F] continuously,
periodically at +45° C [113° F]
-25° C to +65°/70° C [-13°-149°/158° F] for
storage/ transport
Ground and short-circuit protection
90.5
111.8
104.1
125.4
104.1
125.4
®
is a registered Danfoss trademark.
VLT
®
Automation Drive FC 300
Instruction Manual High Power
P160
P200
500
600
20 (3)
4
4
0.98
3910
4625
5119
5893
0.7
122.9
137.7
136.3
151.3
136.3
151.3

Advertisement