Danfoss VLT FC 300 Instruction Manual page 112

Automation drive
Hide thumbs Also See for VLT FC 300:
Table of Contents

Advertisement

5. General Specifications
Safe stop Terminal 37
Voltage level
Voltage level, logic'0' PNP
Voltage level, logic'1' PNP
Nominal input current at 24 V
Nominal input current at 20 V
Input capacitance
All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage
terminals.
1) Terminals 27 and 29 can also be programmed as output.
2) Except safe stop input Terminal 37.
3) Terminal 37 can only be used as safe stop input. Terminal 37 is suitable for category 3 in-
5
stallations in accordance with EN 954-1 (safe stop according to category 0 EN 60204-1), and as
required by the EU Machinery Directive 98/37/EC. Terminal 37 and the safe stop function are
designed in accordance with EN 60204-1, EN 50178, EN 61800-2, EN 61800-3 and EN 954-1.
For correct and safe use of the Safe Stop function, follow the related information and instructions
in the Design Guide.
Analog inputs:
Number of analog inputs
Terminal number
Modes
Mode select
Voltage mode
Voltage level
Input resistance, R
Max. voltage
Current mode
Current level
Input resistance, R
Max. current
Resolution for analog inputs
Accuracy of analog inputs
Bandwidth
The analog inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage
terminals.
112
3)
(Terminal 37 is fixed PNP logic):
i
i
MG.33.U1.22 - VLT
®
is a registered Danfoss trademark.
VLT
®
Automation Drive FC 300
Instruction Manual High Power
0-24 V DC
< 4 V DC
>20 V DC
50 mA rms
60 mA rms
Voltage or current
Switch S201 and switch S202
Switch S201/switch S202 = OFF (U)
-10 - +10 V (scalable)
approx. 10 kΩ
Switch S201/switch S202 = ON (I)
0/4 to 20 mA (scalable)
approx. 200 Ω
10 bit (+ sign)
Max. error 0.5% of full scale
400 nF
2
53, 54
± 20 V
30 mA
100 Hz