Operating Modes; Mode "On Line" (Inverter Mode); Mode "Standby - ABB Conceptpower DPA 500 Operating Manual

100-500 kw
Hide thumbs Also See for Conceptpower DPA 500:
Table of Contents

Advertisement

6.6

Operating modes

6.6.1

Mode "ON LINE" (INVERTER MODE)

The ON-LINE-Mode is the UPS-Operating Mode in which the load is supplied through the RECTIFIER
and INVERTER.
Using the control panel the UPS can easily be transferred to the ON-LINE-Mode. The ON-LINE-Mode
provides the highest degree of protection, especially in the event of a mains disturbance or failure.
This operating mode is always recommended if the critical loads (computer systems) will not tolerate
any interruption of the supply (not even the shortest). In the unlikely event of an inverter fault or
overload condition the UPS will transfer the load automatically and without interruption to the static
bypass-mains supply (transfer time = 0).
6.6.2

Mode "Standby"

The Standby mode is part of the Xtra VFI operating mode
Standby mode have the INVERTER OFF.
The Xtra VFI operating mode switches the modules from ON-LINE to Standby or from Standby back
to ON-LINE fully automatically. Read through the
works.
Modifications reserved
Page 57/94
LED Indicator
LINE 1
LINE 2
BYPASS
INVERTER
BATTERY
(see Appendix
A). Modules that are in
LED Indicator
LINE 1
LINE 2
BYPASS
INVERTER
BATTERY
Appendix A
in order to fully understand how Xtra VFI
Color
Green
Green
OFF
Green
Green
Color
Green
Green
OFF
Orange
Green