October 2016

4. Ensure proper grounding. It is important that the instrument cable shield:
Be trimmed close and insulated from touching the transmitter housing
Be connected to the next shield if cable is routed through a junction box
Be connected to a good earth ground at the power supply end
5. Plug and seal unused conduit connections.
6. If applicable, install wiring with a drip loop. Arrange the drip loop
so the bottom is lower than the conduit connections and the
transmitter housing.
7. Replace the housing cover.
Figure 6. Terminals
A
A. Power terminals
B. Ground terminal
B
Quick Start Guide
9