Emerson Rosemount 2051 Quick Start Manual page 20

Rosemount 2051cf series. pressure transmitter and rosemount 2051cf series flowmeter with profibus pa protocol
Hide thumbs Also See for Rosemount 2051:

Advertisement

Quick Start Guide
Table 8. Input Parameters
Parameter
Inductance L
Special Conditions for Safe Use (X):
1. If the equipment is fitted with an optional 90 V transient suppressor, it is incapable of
withstanding the 500 V isolation from earth test and this must be taken into account
during installation.
2. The enclosure may be made of aluminum alloy and given a protective polyurethane
paint finish; however care should be taken to protect it from impact and abrasion when
located in Zone 0.
N7 IECEx Type n
Certificate: IECExBAS08.0046X
Standards: IEC60079-0:2011, IEC60079-15:2010
Markings: Ex nA IIC T4 Gc (–40 °C ≤ T
Special Condition for Safe Use (X):
1. If fitted with a 90 V transient suppressor, the equipment is not capable of withstanding
the 500 V electrical strength test as defined in clause 6.5.1 of IEC60079-15:2010. This
must be taken into account during installation.
7.6 Brazil
E2 INMETRO Flameproof
Certificate: UL-BR 14.0375X
Standards: ABNT NBR IEC60079-0:2008 + Errata 1:2011,
Markings: Ex d IIC T6/T5 Gb IP66, T6(–50 °C ≤ T
Special Conditions for Safe Use (X):
1. The device contains a thin wall diaphragm. Installation, maintenance and use shall take
into account the environmental conditions to which the diaphragm will be subjected.
The manufacturer's instructions for installation and maintenance shall be followed in
detail to assure safety during its expected lifetime.
2. The Ex d blanking elements, cable glands, and wiring shall be suitable for a temperature
of 90 °C.
3. In case of repair, contact the manufacturer for information on the dimensions of the
flameproof joints.
I2 INMETRO Intrinsic Safety
Certificate: UL-BR 14.0759X
Standards: ABNT NBR IEC 60079-0:2008 + Errata 1:2011; ABNT NBR IEC 60079-11:2009
Markings: Ex ia IIC T4 Ga (–60 °C ≤ T
Table 9. Input Parameters
Parameter
Voltage U
Current I
i
Power P
i
Capacitance C
20
FISCO
0 mH
i
ABNT NBR IEC 60079-1:2009 + Errata 1:2011,
ABNT NBR IEC 60079-26:2008 + Errata 1:2009
HART
30 V
i
200 mA
1 W
12 nF
i
≤ +70 °C)
a
≤ +65 °C), (–50 °C ≤ T
a
≤ +70 °C)
a
Fieldbus/PROFIBUS
30 V
300 mA
1.3 W
0
October 2016
≤ +80 °C)
a