Quick Start Guide
5.3 Class 2 Master
The Rosemount 2051 PROFIBUS DD and DTM files are available at
EmersonProcess.com/Rosemount
Table 3
for steps to configure the transmitter for Pressure measurement. See
Rosemount 2051
Table 3. Pressure Configuration via Class 2 Master
Steps
Set blocks to Out of Service
Select Measurement Type
Select Units
Enter Scaling
Set blocks to Auto
5.4 Host integration
Control host (Class 1)
The Rosemount 2051 device utilizes condensed status as recommended by the
Profile 3.02 specification and NE 107. See manual for condensed status bit
assignment information.
The appropriate GSD file must be loaded on the control host - Rosemount 2051
specific (rmt3333.gsd) or Profile 3.02 Generic (pa139700.gsd). These files can be
found on
EmersonProcess.com/Rosemount
Configuration host (Class 2)
The appropriate DD or DTM file must be installed in the configuration host. These
files can be found at EmersonProcess.com/Rosemount.
14
or by contacting your local salesperson. See
Reference Manual
Actions
Put Transducer Block into Out of Service mode
Put Analog Input Block into Out of Service mode
Set Primary Value type to Pressure
Set Engineering Units
- Primary and secondary units must match
Set Scale In in Transducer Block to 0–100
Set Scale Out in Transducer Block to 0–100
Set PV Scale in Analog Input Block to 0–100
Set Out Scale in Analog Input Block to 0–100
Set Linearization in Analog Input Block to No Linearization
Put Transducer Block into Auto mode
Put Analog Input Block into Auto mode
for Flow or Level configuration instructions.