October 2016
Table 9. Input Parameters
Parameter
Inductance L
Special Conditions for Safe Use (X):
1. If the equipment is fitted with an optional 90 V transient suppressor, it is incapable of
withstanding the 500 V insulation from earth test and this must be taken into account
during installation.
2. The enclosure may be made of aluminium alloy and given a protective polyurethane
paint finish; however care should be taken to protect it from impact and abrasion when
located in atmospheres that require ELP Ga.
IB INMETRO FISCO
Certificate: UL-BR 14.0759X
Standards: ABNT NBR IEC 60079-0:2008 + Errata 1:2011; ABNT NBR IEC 60079-11:2009
Markings: Ex ia IIC T4 Ga (–60 °C ≤ T
Table 10. Input Parameters
Parameter
Voltage U
Current I
i
Power P
i
Capacitance C
Inductance L
Special Conditions for Safe Use (X):
1. If the equipment is fitted with an optional 90 V transient suppressor, it is incapable of
withstanding the 500 V insulation from earth test and this must be taken into account
during installation.
2. The enclosure may be made of aluminium alloy and given a protective polyurethane
paint finish; however care should be taken to protect it from impact and abrasion when
located in atmospheres that require ELP Ga.
7.7 China
E3 China Flameproof
Certificate: GYJ13.1386X; GYJ15.1366X [Flowmeters]
Standards: GB3836.1-2010, GB3836.2-2010, GB3836.20-2010-2010
Markings:
Pressure Transmitter: Ex d IIC Gb, T6(–50 °C ≤ T
Flowmeter: Ex d IIC Ga/Gb, T6(–50 °C ≤ T
Special Conditions for Safe Use (X):
1. Symbol "X" is used to denote specific conditions of use:
a. The Ex d blanking elements, cable glands, and wiring shall be suitable for a
temperature of 90 °C.
b. This device contains a thin wall diaphragm. Installation, maintenance and use shall
take into account the environment conditions to which the diaphragm will be
subjected.
HART
0
i
FISCO
17.5 V
i
380 mA
5.32 W
0 nF
i
0 μH
i
Fieldbus/PROFIBUS
0
≤ +60 °C)
a
≤ +65 °C), T5(–50 °C ≤ T
a
≤ +65 °C), T5(–50 °C ≤ T
a
Quick Start Guide
≤ +80 °C)
a
≤ +80 °C)
a
21