7.6
Gas conversion
models can be transformed from operating
UNIQA REVOLUTION
with G20 (methane) to G30/G31 (LPG), by installing the "Nozzle
kit for G30/G31" code 8059250, to be ordered separately from
the boiler, , also modifying "PAR 03" .
m
CAUTION
The maintenance interventions described must ONLY
be carried out the professionally qualified personnel.
a
WARNING
Before carrying out any interventions described:
– set the main system switch to "OFF"
– close the gas valve
– make sure that no hot parts inside the appliance are
touched.
OFF
7.6.1
Preliminary operations
To carry out the conversion:
– remove the screws (1), pull the front panel (2) forwards and
release it from the top by lifting it
2
Fig. 43
1
Fig. 44
– remove the screws (3) securing the control panel (4)
– move the panel (4) upwards (a) but keeping it in the side
guides (5) to the end of travel
– bring it forwards and down (b) until it is horizontal
4
b
3
– unscrew the screws (6) and remove the panel (7) carefully
6
7
5
a
Fig. 45
Fig. 46
37