Using the SSI_Absolute_Encoder technology object
4.5 Programming the SSI_Absolute_Encoder
4.5.6
Error codes of parameter ErrorID
Error code
Description
(W#16#...)
0000
No error
Error messages from technology module
80A1
POWER_ERROR from feedback interface: Incorrect supply voltage L+
80A2
ENC_ERROR from feedback interface: Incorrect encoder signal
80A3
LD_ERROR from feedback interface: Error when loading via control interface
Error messages of the instruction SSI_Absolute_Encoder
80B8
New comparison value 0 does not meet the following conditions:
Low counting limit <= comparison value 0 <= high counting limit
•
Comparison value 0 < comparison value 1
•
80B9
New comparison value 1 does not meet the following conditions:
Low counting limit <= comparison value 1 <= high counting limit
•
Comparison value 0 < comparison value 1
•
80C0
Instruction was called multiple times with the same instance (DB)
80C1
Communication with technology module failed (read data records): Error information of internal in-
struction RDREC saved in static tag AdditionalErrorID
80C2
Communication with technology module failed (write data records): Error information of internal in-
struction WRREC saved in static tag AdditionalErrorID
80C5
Reading of the current start information of the OB failed: Error information of internal instruction
RD_SINFO saved in static tag AdditionalErrorID
80C6
Failed to get I/O addresses of the technology module: Error information of internal instruction
RD_ADDR saved in static tag AdditionalErrorID
80C7
Module not inserted or no supply voltage L+
164
Counting, measurement and position detection
Function Manual, 12/2017, A5E32009889-AG