Lost hardware interrupt
If an event occurs which is supposed to trigger a hardware interrupt but the previous,
identical event has not yet been processed, no further hardware interrupt is triggered. The
hardware interrupt is lost. This may lead to the "Hardware interrupt lost" diagnostic interrupt,
depending on the parameter assignment.
Hardware interrupts that can be activated
Hardware
Available in counting
interrupt
mode using
Incremen-
tal or pulse
encoder
New Capture
Yes
value availa-
ble
Synchroniza-
Yes
tion of the
counter by an
external signal
Gate start
Yes
Gate stop
Yes
Overflow (high
Based on
counting limit
counter
violated)
value
Underflow
Based on
(low counting
counter
limit violated)
value
Direction
Based on
reversal*
counter
value
Zero crossing
Based on
counter
value
178
Available in measuring
mode using
SSI abso-
Incremen-
lute en-
tal or pulse
coder
encoder
Yes
No
No
Yes
No
Yes
No
Yes
No
Based on
counter
value
No
Based on
counter
value
Based on
Based on
position
counter
value
value
Based on
Based on
position
counter
value
value
Available in
operating
mode Position
SSI abso-
input for "Mo-
lute en-
tion Control"
coder
technology
object
No
No
No
No
No
No
No
No
No
No
No
No
Based on
No
position
value
Based on
No
position
value
Description
Hardware interrupt when
current counter value or
position value is saved as
Capture value
Hardware interrupt upon
synchronization of the
counter by signal N or DI
edge
Hardware interrupt when
internal gate opens
Hardware interrupt when
internal gate closes
Hardware interrupt when
counter value exceeds
high counting limit
Hardware interrupt when
counter value falls below
low counting limit
Hardware interrupt when
counter value or position
value changes direction
Hardware interrupt with
zero crossing of counter
value or position value
Counting, measurement and position detection
Function Manual, 12/2017, A5E32009889-AG
Event
Type
number
8
9
1
2
3
4
10
7