4.4.4

Behavior of a DI (SSI_Absolute_Encoder)

Setting function of the DI
By configuring a digital input, you specify which functions the digital input triggers at
switching.
You can select from the following options:
Function of a digital
Meaning
input
Capture (Page 33)
The configured edge at the respective digital input saves the
current position value as a Capture value. The technology
object displays the Capture value at the output parameter
CapturedValue.
The function can only be used for one of the two digital inputs.
Digital input without
No technological function is assigned to the respective digital
function
input.
You can read the signal state of the digital input via the re-
spective static variable (Page 165) of the technology object:
Note
You can choose the "Capture" function only in operating mode "Use position value (SSI
absolute value) as reference".
Input delay
By configuring the input delay, you suppress interferences at the digital inputs. Signals with a
pulse duration below the configured input delay are suppressed.
You can select from the following input delays:
● None
● 0.05 ms
● 0.1 ms (default)
● 0.4 ms
● 0.8 ms
● 1.6 ms
● 3.2 ms
● 12.8 ms
● 20 ms
Counting, measurement and position detection
Function Manual, 12/2017, A5E32009889-AG
UserStatusFlags.StatusDI0
UserStatusFlags.StatusDI1
Using the SSI_Absolute_Encoder technology object
4.4 Configuring SSI_Absolute_Encoder
Additional option-specific parame-
ters
Input delay
Edge selection
Input delay
145