(3) EPO Connection:
User can select the polarity of EPO, EPO is Normally close as default setting.
Normally Open
Normally the EPO connector is open on the rear panel. Once the connector is
closed with a wire, the UPS will cut off the output until the EPO status is disabled.
Disable the EPO status
Normally Closed
Normally the EPO connector is closed with a wire on the rear panel. Once
the connector is open, the UPS will cut off the output until the EPO status is
disabled.
Enable the EPO status

5.3 Battery charging

Fully charge the batteries by leaving the UPS connected to the mains for 4-6
hours. You may use the UPS directly without charging it but the stored
energy time may be shorter than the nominal value specified.

5.4 Turn on the UPS

(1) With utility power available:
UPS will get into inverter mode, the LCD screen will indicate the status of the
UPS.
(2) With utility power not available:
In order for the UPS to be cold started without utility power available, the
user needs
tinuously for more than 1 second to turn on the UPS, the
Enable the EPO status
Disable the EPO status