Operation - AccuLine CNQplus 1000RT User Manual

Rack/tower 1000/2000/3000va online ups
Table of Contents

Advertisement

Note: Three or more EBMs can be connected to the UPS in the same way as
shown above.
Note: After connecting the EBMs, please do not forget to set the number of
EBMs via the LCD menu
for setting procedure. If you are using non-standard EBMs, please call local
dealer or distributor for setting method.

1.2 Operation

Do not disconnect the mains cable from the UPS or the building wiring
socket (ground-connected shockproof socket) during operation as this
would suspend ground connection of the UPS and all connected loads
and EBMs.
The UPS features its own, internal current source (batteries). You may be
electric shocked when you touch the UPS output sockets or output
terminal block even if the UPS is not connected to the building wiring
socket.
In order to fully disconnect the UPS, first press the OFF button to turn off
the UPS, then disconnect UPS from the mains.
Ensure that no liquid or other foreign objects can enter the UPS.
Do not remove the enclosure. This system is to be serviced by qualified
service personnel only.
Remove the protective panel only after disconnecting the terminal
connections.
For CNQplus-3000SRT input wire, use 90 C copper wire 3 x 4 mm² and
0,5 N-m (4.4 lb-in) Torque force when connecting to terminal block.
9
E
B
D
A