Battery Recharge - AccuLine TNplus 1000m User Manual

1000va / 2000va / 3000va uninterruptible power supply systems
Table of Contents

Advertisement

(4) EPO Connection:
The EPO (Emergency Power Off) function is a standard feature
of the UPS and the polarity of the EPO is configurable; EPO is
normally close as default setting. If the connection between the
two ports of the EPO connector is disconnected, the EPO
function will be active and the UPS will cut off its output power
immediately.
Normally open
In normal (Line) mode, the EPO connector on the rear panel is
open. Once the two ports of connector are closed with a wire, the
UPS will cut off its output until the EPO status is reset.
Disable EPO status
In normal (Line) mode, the two ports of the EPO connector on
the rear panel are closed with a wire. Once the connector is open,
the UPS will cut off its output until the EPO status is disabled.
Enable EPO status

5.3 Battery recharge:

Fully charge the batteries of the UPS system by leaving it connected to
the mains power for approximately 4-6 hours. The UPS system is able
to operate directly without recharging process, but the backup time may
be shorter than the nominal value specified.
d
-16-
Enable EPO status
Disable EPO status

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tnplus 1000lmTnplus 2000lmTnplus 3000mTnplus 3000lmTnplus 3000m pro

Table of Contents