the UPS output to less than 90% of its nominal power capacity.
Note: Please follow the following steps to connect a generator
Activate the generator and wait until the operation is stable before supplying
power of the generator to the UPS (be sure that the UPS is in idle mode).
Then turn on the UPS according to the start-up procedure. After the UPS is
turned on, then the loads can be connected to the UPS one by one.
6.2 Battery mode
The LCD display in battery mode is shown in the following diagram.
Information about the utility power, the battery level, the UPS output and the
load level will be displayed. The bATT string indicates that the UPS is
operating in battery mode.
When the UPS is in battery mode, the buzzer beeps once every 4 seconds. If
more than 1 second to resume the alarm function.
Battery mode
6.3 Bypass mode
The LCD display in bypass mode is shown in the following diagram.
Information about the utility power, the battery level, the UPS output and the
load level will be displayed. The UPS will beep once every 2 minutes in
bypass mode. The bYPA string indicates that the UPS is in bypass mode.
25