Connecting multiple EBMs in Tower form
1. Connect Earth line between the UPS and the first EBM, then connect the
Earth Line between the first EBM and the second EBM.
2. Take off the front panel, and connect the battery terminal (A) from the UPS
to EBM terminal (B) shown as below. hen connect the battery terminal (D)
of the first EBM to the battery terminal (E) of the second EBM. Users need
to remove the small gate(C) on side of the front panel to allow the outlet
wire of the EBM to pass through the gate and then reassemble front panel.
Connecting Multiple EBMs in rack form
1. Connect the earth line between the UPS and the first EBM, and then
connect the earth Line between the first EBM and the second EBM.
2. Take off the front panel, and connect the battery terminal (A) from UPS to
EBM terminal (B) shown as below. hen connect the battery terminal (D)
from the first EBM to the battery terminal (E) from the second EBM. Users
need to remove the small gate (C) on side of the front panel to allow the
outlet wire of the EBM to pass through the gate and then reassemble front
panel.
8