Here is a example for changing the Operating mode from normal mode to
converter mode through the LCD panel.
Step 1: OPV after pressing the Enter button;
Step 3: bYPA after pressing the Select button;
Step 5: ECO flickering after pressing
the Select button;
Step 2: OPF after pressing the Select button.
Step 4: MOdE after pressing the Select button,
press the Enter button to set mode, then UPS
will be flickering;
Step 6: CVF flickering after pressing the
Select again. Press the Enter button to
confirm changing the mode. Touch the
Enter button instantly to exit setting mode.
30