Trouble Shooting - AccuLine CNQplus 1000RT User Manual

Rack/tower 1000/2000/3000va online ups
Table of Contents

Advertisement

8. Trouble Shooting

If the UPS system does not operate correctly, check the operating status on
the LCD display.
Warning
Site fail
Fan fail
Battery over voltage
(over charged)
Battery low
Charge fail
Inverter temperature high
Ambient temperature high
Battery open
Overload
EPO
Battery fault
If the UPS system does not operate correctly, please attempt to solve the
problem using the table below.
Problem
No indication, no
warning tone even
though system is
connected to
mains power
supply
Display Mode
LCD, even though
the power supply
is available
Display Mode
LCD, and audible
alarm sounding
every 1 beep in
every 4 seconds
String
SITE
FANF
HIGH
bLOW
CHGF
TEPH
AMbH
bOPN
OVLD
EPO
bATF
Possible cause
No input voltage
Inverter not switched
on
Mains power supply
has failed, or Input
power and/or
frequency are out of
tolerance
31
Fault
Inverter short
Overload fault
Inverter soft start fail
Bus soft start fail
Over temperature fault
Inverter voltage low
Inverter voltage high
Bus voltage over
Bus voltage Low
Bus voltage unbalance
Bus short
NTC open
Remedy
Check building wiring socket
outlet and input cable.
Press On-
Switching to battery mode
automatically.
Check input power source
and inform dealer if
necessary.
String
SHOR
OVLD
ISFT
bSFT
OVTP
INVL
INVH
bUSH
bUSL
bUSE
bUSS
NTCO

Hide quick links: