External motor temperature sensor
(for all units)
Don't install temperature sensor
wires with other control wires.
Must use double shield when running
temperature sensor wires with motor
wires
Braking resistor
Braking resistor
with line side over
temperature cutoff
This is the only
way to turn off
voltage to the
resistor in the
event of failure of the
internal
braking
transistor of the inverter.
Braking module
Connection of Power Circuit
On F5 B/G units it is necessary to activate the function through
parameter CP.28.
T1
T2
F5-M/S:
Bridge, when no
sensor is connected
++
PB
U
24VDC or 120VAC contactor control voltage
Note: a NC thermal switch not PTC device on the resistor is required.
++
- -
T1
T2
Thermal switch
(NC-contact)
T1
Optional Connection
connect only when resistor has valid temperature
T2
sensor, e.g. back mount resistors
PA
PB
= 90°C
OH1
OH2
+
PA
GTR7
-
PB
T1
T2
Temperature sensor (PTC )
1650Ω...4kΩ tripping resistance
750Ω...1650Ω reset resistance
X1A
L1
N/L2
L3
++
--
PB
U
V
W
T1
T 2