Analog Modules
Default settings for measuring range module
The measuring range modules are preset to "B" (voltage; " 10 V) when the
module is supplied.
To use the following preset measuring methods and measuring ranges, you only
have to change the measuring range module to the corresponding setting.
Parameter assignment in STEP 7 is not necessary.
Table 4-64 Default Settings of the SM 331; AI 8 x 12 bits Using Measuring Range Modules
Measuring Range
Module Setting
Parameter
You will find a description of the general procedure for assigning parameters to
analog modules in Section 4.7.
An overview of the parameters that you can set and their default settings are
shown in the table below.
Table 4-65 Parameters of the SM 331; AI 8 x 12 bits
Parameter
Enable
•
Diagnostic interrupt
•
Hardware interrupt
upon limit violation
Trigger for hardware
interrupt
•
Upper limit value
•
Lower limit value
Diagnostics
•
Group diagnostics
•
With wire-break
check
4-120
Measuring Method
A
B
C
Four-wire transmitter
D
Two-wire transmitter
Value Range
Yes/no
Yes/no
Constraint possible due to measuring
range.
From 32511 to –32512
–32512 to 32511
Yes/no
Yes/no
Voltage
Voltage
Current,
Current,
Default
Settings
No
No
–
No
No
Programmable Logic Controllers S7-300 Module Data
Measuring Range
" 1000 mV
" 10 V
4 to 20 mA
4 to 20 mA
Para-
Scope
meter
Type
Dynamic
Module
Dynamic
Channel
Channel
Static
group
A5E00105505-03