Technical specifications of the SM 322; DO 8 x 48-125 VDC/1.5 A
Dimensions and Weight
Dimensions W x H x D
(in millimeters)
Weight
Data for Specific Module
Supports clocked
operation
Number of outputs
Length of cable
•
Unshielded
•
Shielded
Voltages, Currents, Potentials
Rated load voltage L+
•
Reverse polarity protection
Total current of the outputs
(per group)
•
Horizontal configuration
Up to 40 _C
Up to 50 _C
Up to 60 _C
•
Vertical configuration
Up to 40 _C
Isolation
•
Between channels and
backplane bus
•
Between the channels
In groups of
Permitted potential difference
•
Between the different
circuits
Insulation tested with
Current consumption
•
From the backplane bus
•
From the load voltage L+
(no load)
Power dissipation of the module typ. 7.2 W
Status, Interrupts, Diagnostics
Status display
Interrupts
Diagnostic functions
•
Group error display
Programmable Logic Controllers S7-300 Module Data
A5E00105505-03
40 x 125 x 117
Approx. 250 g
No
8
max. 600 m
max. 1000 m
48 VDC to 125 VDC
Yes, by means of
1)
fuse
max. 6 A
max. 4 A
max. 3 A
max. 4 A
Yes
Yes
4
146 VDC / 132 VAC
1500 VAC
max. 100 mA
max. 2 mA
1)
Green LED per channel
None
2)
2)
Red LED (SF)
3)
Data for Selecting an Actuator
Output voltage
•
At " 1" signal
Output current
•
At " 1" signal
Rated value
Permitted range
•
Permitted surge current
•
For "0" signal
(leakage current)
Output delay (for resistive load)
•
From " 0" to "1"
•
At "1" to "0"
Lamp load
Parallel connection of
2 outputs
•
For redundant actuation of
a load
•
To increase performance
Triggering a digital input
Switch rate
•
For resistive load
•
For inductive load
•
For lamp load
Limit (internal) of the in
ductive circuit interruption
voltage up
Short-circuit protection of the
output
•
Threshold on
Replacement fuses
•
Schurter
•
Wickman
Fuse carrier
•
Wickman
The fuses on this module are merely
supplementary fuses. External overcurrent
protection (suitable for branch circuits conforming
to the local regulations for electrical engineering)
is required in the supply cables of the load circuit.
Potential errors are:
- No load voltage
- Fuse defective
- Output overloaded
If an overload condition is detected, the output is
inhibited for approximately 2.4 s.
Digital Modules
min. L + (–1.,2 V)
1.5 A
10 mA to 1.5 A
max. 3 A for 10 ms
max. 0.5 mA
max. 2 ms
max. 15 ms
max. 15 W at 48 V
max. 40 W at 125 V
Possible (only outputs
of the same group)
Not possible
Possible
max. 25 Hz
max. 0.5 Hz
max. 10 Hz
typ. M (–1V)
3)
Yes, electronic
typ. 4.4 A
Fuse 6.,3 A/250 V,
quick blow, 5 x 20 mm
SP0001.1012
194-1630-0
653 0000 040
3-83