Output Ranges Of The Analog Output Module Sm 332; Ao 4 X 16 Bits - Siemens SIMATIC S7-300 Reference Manual

Programmable logic controllers module data
Hide thumbs Also See for SIMATIC S7-300:
Table of Contents

Advertisement

4.27.3
Output Ranges of the Analog Output Module SM 332;
AO 4 x 16 bits
Connecting the analog outputs
You can connect the outputs as voltage or current outputs, or disable them. You
perform connection of the outputs with the "output type" parameter in STEP 7.
Unused Channels
So that unused output channels of the SM 332; AO 4 x 16 bits remain
de-energized, you must set the "output type" parameter to "disabled" and leave the
terminal open.
Output ranges
You program the output ranges for voltage and current outputs in STEP 7.
Table 4-84 Output Ranges of the Analog Output Module SM 332;
Selected Type of Output
Voltage
Current
Default Settings
The default settings of the module are "Voltage" for the output type and "" 10 V"
for the output range. You can use this combination of output type and output range
without parameterizing the SM 332; AO 4 x 16 bits in STEP 7.
Substitute values
You can configure the SM 332; AO 4 x 16 bits for the CPU operating mode STOP
as follows: Outputs De-energized, Hold Last Value or Inject Substitute Values. If
you inject substitute values, they must be within the output range.
Programmable Logic Controllers S7-300 Module Data
A5E00105505-03
x
AO 4
16 bits
1 to 5 V
0 to 10 V
" 10 V
From 0 to 20 mA
From 4 to 20 mA
" 20 mA
Output Range
Analog Modules
Description
You will find the digital
analog values in section
4.3.2 in the reference
4.3.2 in the reference
manual in the voltage and
manual in the voltage and
current output ranges
4-175

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents