Commissioning The Sm 331; Ai 8 X Rtd - Siemens SIMATIC S7-300 Reference Manual

Programmable logic controllers module data
Hide thumbs Also See for SIMATIC S7-300:
Table of Contents

Advertisement

4.23.1

Commissioning the SM 331; AI 8 x RTD

You set the mode of operation of the SM 331; AI 8 x RTD in STEP 7.
Parameter
You will find a description of the general procedure for assigning parameters to
analog modules in Section 4.7.
Parameterization restrictions when using the SM 331; AI 8 x RTD with
PROFIBUS masters that only support DPV0.
When you use the analog input module SM 331; AI 8 x RTD in an ET 200M
PROFIBUS slave system with a PROFIBUS master which is not an S7 master,
certain parameters are not permitted. Masters that are not S7 masters do not
support hardware interrupts. So all the parameters associated with these functions
are deactivated. The deactivated parameters are hardware interrupt enable,
hardware restrictions and end-of-scan-cycle interrupt enable. All the other
parameters are permitted.
An overview of the parameters that you can set and their default settings are
shown in the table below.
Table 4-68 Parameters of the SM 331; AI 8 x RTD
Parameter
Enable
Diagnostic interrupt
Hardware interrupt
upon limit violation
Hardware interrupt at
end of cycle
Trigger for hardware
interrupt
Upper limit value
Lower limit value
Diagnostics
Group diagnostics
With wire-break
check
Programmable Logic Controllers S7-300 Module Data
A5E00105505-03
Value Range
Yes/no
Yes/no
Yes/no
32511 to –32512
–32512 to 32511
Yes/no
Yes/no
Analog Modules
Default
Para-
Settings
meter
Type
No
No
Dynamic
No
32767
Dynamic
-32768
No
Static
No
Scope
Module
Channel
Channel
group
4-129