Siemens SIMATIC S7-300 Reference Manual page 152

Programmable logic controllers module data
Hide thumbs Also See for SIMATIC S7-300:
Table of Contents

Advertisement

Digital Modules
Dimensions and Weight
Dimensions W x H x D
(in millimeters)
Weight
Data for Specific Module
Supports clocked
operation
Number of outputs
Length of cable
Unshielded
Shielded
Voltages, Currents, Potentials
Rated load voltage L1
All load voltages must be of the
same phase
Total current of the outputs
(per group)
Horizontal configuration
Up to 40 _C
Up to 60 _C
Vertical configuration
Up to 40 _C
Isolation
Between channels and
backplane bus
Between channels
In groups of
Permitted potential difference
Between M
and the
internal
outputs
Between the outputs of the
different groups
Insulation tested with
Current consumption
From the backplane bus
From load voltage L+
(without load)
Power dissipation of the module typ. 8.6 W
Status, Interrupts, Diagnostics
Status display
Interrupts
Diagnostic interrupt
Diagnostic functions
Group error display
3-68
40 x 125 x 117
Approx. 275 g
No
16
max. 600 m
max. 1000 m
120/230 VAC
max. 4 A
max. 2 A
max. 2 A
Yes
Yes
8
500 VAC
230 VAC
4000 VDC
max. 200 mA
max. 2 mA
Green LED per channel
No
Red LED (SF)
(fuse or no L1/N)
Data for Selecting an Actuator
Output voltage
At signal "1"
Output current
At signal "1"
Rated value
Permitted range for 0° C to
40° C
Permitted range for 0° C to
60° C
Permitted surge current
(per group)
At signal "0"
(leakage current)
Inhibit voltage
Zero cross inhibit voltage
Size of the motor starter
Lamp load
Connecting two outputs in
parallel
For redundant triggering
of a load
To increase
performance
Triggering a digital input
Switch rate
For resistive load
Inductive loads,
according to
IEC 947-5-1, AC 15
For lamp load
Short-circuit protection of output Fuse 8 A,
Min. current required for
fuse to blow
Max. response time
Replacement fuses
Wickman
Schurter
Littlefuse
Fuse carrier
Wickman
Programmable Logic Controllers S7-300 Module Data
min. L + (–0.8 V)
1 A
10 mA to 1 A
10 mA to 0.5 A
max. 20 A
(with 2 half-waves)
max. 2 mA
max. 60 V
max. size 4 to NEMA
max. 50 W
Possible (only outputs
of the same group)
No
Possible
max. 10 Hz
max. 0.5 Hz
max. 1 Hz
250 V; per group
min. 40 A
max. 300 ms
8 A fuse, quick-acting
19 194-8 A
SP001.1014
217.008
19 653
A5E00105505-03

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents