Technical specifications of the SM 322; DO 8 x 120/230 VAC/2 A ISOL
Dimensions and Weight
Dimensions W x H x D
Weight
Data for Specific Module
Supports clocked
operation
Number of outputs
Length of cable
Unshielded
Shielded
Voltages, Currents, Potentials
Rated load voltage L1
Total current of the outputs
(module)
Horizontal configuration
Up to 40 °C
Up to 60 °C
Vertical configuration
Up to 40 °C
Isolation
Between channels and
backplane bus
Between channels
In groups of
Permitted potential difference
Between M
and the
internal
outputs
Between outputs
Insulation tested with
Between M
and the
internal
outputs
Between the outputs of the
different groups
Current consumption
From the backplane bus
From load voltage L1
(without load)
Power dissipation of the module typ. 8.6 W
Status, Interrupts, Diagnostics
Status display
Interrupts
Diagnostic interrupt
Diagnostic functions
Group error display
Programmable Logic Controllers S7-300 Module Data
A5E00105505-03
40 x 125 x 117
Approx. 275 g
No
8
max. 600 m
max. 1000 m
120/230 VAC
max. 8 A
max. 4 A
max. 4 A
Yes
Yes
1
230 VAC
500 VAC
1500 VAC
2000 VAC
max. 100 mA
max. 2 mA
Green LED per channel
Parameters can be
assigned
Red LED (SF)
Data for Selecting an Actuator
Output voltage
At signal "1"
Output current
At signal "1"
Rated value
Permitted range for 0 °C to
40 °C
Permitted range for
40 °C to 60 °C
Permitted surge current
(per group)
For "0" signal
(leakage current)
Zero cross inhibit voltage
Size of the motor starter
Lamp load
Connecting two outputs in
parallel
For redundant triggering of
a load
To increase performance
Triggering a digital input
Switch rate
For resistive load
Inductive loads, according
to IEC 947-5-1, AC 15
For lamp load
Short-circuit protection of output Yes,
Digital Modules
min. L1 (–8.5 V)
2 A
10 mA to 2 A
10 mA to 1 A
max. 20 A
(with 2 half-waves)
max. 2 mA
max. 60 V
max. size 5 to NEMA
max. 50 W
Possible
Not possible
Possible
max. 10 Hz
max. 0.5 Hz
max. 1 Hz
3.15 A /
250 V fuse, fast-acting